| Plan Review Notes For Permit 05090750 |
| Permit Number |
05090750 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-09-19 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} SEE 220.12(B) FOR CALCULATING TRACK | | | LIGHTING LOADS, AND 215.3 FOR CONTINUOUS | | | LOADS. | | | | | | 2} SHOW REQUIRED EXIT AND EMERGENCY | | | LIGHTING ON PLANS WITH CIRCUIT NUMBERS. | | | | | | 3} PLEASE SEE 220.13 FOR RECEPTACLE | | | CALCULATIONS. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|