| 2005-11-03 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)SHOW ACCESSIBLE PARKING DIMENSIONS |
| | FOR THE SPACE AND THE ACCESS AISLE, |
| | FBC11-4.6.THIS IS SHOWN ON L-1. |
| | |
| | 3.)PROVIDE FINISHED FLOOR ELEVATIONS |
| | OR SLOPE FOR THE ACCESSIBLE ROUTE |
| | (SIDEWALK TO ENTRANCE) AND A RAMP |
| | DETAIL, FBC11-4.8.SHEET ID-0.2. |
| | |
| | 4.) PLEASE DECLARE OCCUPANCY FOR THE |
| | ADJACENT TENANT SPACE. |
| | |
| | 5.) THE BLOCK WALL APPEARS TO BE A |
| | TENANT SEPARATION; PLEASE INDICATE AS |
| | SUCH. SHOW FIRE RATING OF THE EXISTING |
| | TENANT SEPARATION SHOWN; S4-ID4.0 REFERS |
| | TO U419 BUT SHOULD ALSO INDICATE RATING. |
| | INDICATE FIRE RATING OF THE BLOCK WALL. |
| | SHEET ID-2.0 REFERS TO A 1 HOUR |
| | OCCUPANCY SEPARATION OF AN HOUR IN THE |
| | FORM OF A NOTE, AND DOOR B IS SHOWN AS |
| | AN EXISTING FIRE RATED DOOR.SHOW THE |
| | FIRE RATING FOR THE DOOR.NO OCCUPANCY |
| | SEPARATION SHOWN ON THE PLAN. |
| | |
| | 6.)PROVIDE A ROOM DESIGNATION FOR THE |
| | ROOM WHICH HAS ACCESS TO THE EXTERIOR |
| | BUT NOT ACCESS FROM THE OTHER SPACE |
| | (ADJACENT TO THE MODEL KITCHEN). |
| | DECLARE AN OCCUPANCY FOR THIS AREA.IF |
| | IT IS ACCESSORY STORAGE, PROVIDE |
| | INFORMATION AS TO WHAT WILL BE STORED. |
| | SHOW ANY REQUIRED TENANT OR OCCUPANCY |
| | SEPARATIONS. |
| | |
| | 7.)THE MAXIMUM TRAVEL DISTANCE WHEN |
| | SCALED IS 73.5' RATHER THAN 70' AS |
| | INDICATED ON THE PLAN.THE PATH OF |
| | TRAVEL IS SHOWN GOING THROUGH FURNITURE, |
| | SEE ID2.1.ALSO THE PATH OF TRAVEL IN |
| | SOME PLACES IS AGAINST (OR VERY CLOSE |
| | TO) THE WALL; PLEASE SHOW A NATURAL PATH |
| | OF TRAVEL.IF THE TRAVEL DISTANCE |
| | EXCEEDS 75' A SECOND EGRESS DOOR IS |
| | REQUIRED, FBC1020.1(4). |
| | |
| | 8.)IS THIS BUILDING SPRINKLED? PROVIDE |
| | FIRE SPRINKLER PLANS, FBC104.3.1.1. |
| | |
| | 9.)SPECIFY MINIMUM INTERIOR FINISH |
| | CLASSIFICATION, FBC803.2. |
| | |
| | 10.)SHOW EXIT SIGNS, FBC1016.3. |
| | |