2005-09-29 00:00:00*** DENIED ***
 1) AHU #1 RETURN TRANSFER DUCT (BYPASS)
 IN MASTER BEDROOM MUST BE 1 1/2 TIMES
 LARGER THAN SUPPLY AIR, EXP. 12" SUPPLY
 DUCT REQUIRES A 16" RETURN DUCT. PER
 2001 FBC/M 601.4 .
 2) AHU #2 SHOWING ON MECH. PLANS AS 10
 SEER NEEDS TO BE 12 SEER. PER ENERGY
 CAL.
 3) AHU #2 AND RETURN AIR GRILL NOT
 SHOWING ON MECH. PLANS.
 4) DRYER VENT NOT SHOWING ON MECH. PLANS
 (NOTE: DRYER VENT CAN NOT EXHAUST ONTO
 POOL AREA. PER 2001 FBC/M 501.3 .
 5) NEED TO FILE A NOTICE OF
 COMMENCEMENT.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.