| Plan Review Notes For Permit 05090713 |
| Permit Number |
05090713 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-09-29 00:00:00 | *** DENIED *** | | | 1) AHU #1 RETURN TRANSFER DUCT (BYPASS) | | | IN MASTER BEDROOM MUST BE 1 1/2 TIMES | | | LARGER THAN SUPPLY AIR, EXP. 12" SUPPLY | | | DUCT REQUIRES A 16" RETURN DUCT. PER | | | 2001 FBC/M 601.4 . | | | 2) AHU #2 SHOWING ON MECH. PLANS AS 10 | | | SEER NEEDS TO BE 12 SEER. PER ENERGY | | | CAL. | | | 3) AHU #2 AND RETURN AIR GRILL NOT | | | SHOWING ON MECH. PLANS. | | | 4) DRYER VENT NOT SHOWING ON MECH. PLANS | | | (NOTE: DRYER VENT CAN NOT EXHAUST ONTO | | | POOL AREA. PER 2001 FBC/M 501.3 . | | | 5) NEED TO FILE A NOTICE OF | | | COMMENCEMENT. | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719. |
|