Plan Review Notes
Plan Review Notes For Permit 05090713
Permit Number 05090713
Review Stop E
Sequence Number 1
Notes
Date Text
2005-09-28 00:00:00OUTLETS HAVE TO BE MORE THAN 10' AWAY
 FROM THE POOL 680.22A3
  
 LIGHTS CAN NOT BE IN THE SPACE 5' FROM
 THE INSIDE WALL OF THE POOL AND NOT LESS
 THAN 12' ABOVE THE WATER SURFACE.
 680.22B1
  
 ALL METAL PARTS THAT ARE WITHIN 5' OF
 THE POOL SHALL BE BONDED TO THE COMMON
 BONDING GRID FOR THE POOL.680.26B5