| Plan Review Notes For Permit 05090701 |
| Permit Number |
05090701 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2006-05-02 00:00:00 | *********UNSAT ********* | | | | | | 1) NOTE: PLEASE SEE 230.7, SEC'S AND | | | FEEDER IN DISCONNECT "A" IS NOT | | | PERMITTED. | | | PLEASE SEE THAT THE SEC'S TO DISC "B" | | | SHALL BE IN A SEPARATE RACEWAY AND NOT | | | THROUGH DISC "A". | | | | | | 2) NOTE: PLEASE SEE ALL LV SOUND/ SPKR | | | AND LV ITEMS NOT ON ORIGINAL PLANS SHALL | | | BE UNDER A SEPARATE PERMIT WITH SEPARATE | | | LV PLANS. | | | PLEASE KNOW, ALL VALUE FOR TAHT SCOPE OF | | | WORK SHALL ALSO APPLY. | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. | | | ONE ON A REVISION AND ONEUNDER A | | | SEPARATE PERMIT. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|