| Plan Review Notes For Permit 05090701 |
| Permit Number |
05090701 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-12-09 00:00:00 | *** UNSAT *** | | | | | | PLEASE SEE TWO NOTES FROM PREVIOUS | | | REVIEW AND NOTE DUE TO BLD REVIEW. | | | | | | | | | 1)NOTE: PLEASE SEE PLANS STILL INDICATE | | | ONLY ONE DISCONNECT OUTSIDE NEXT TO | | | METER, WHERE-AS RISER SHOWS TWO? | | | PLEASE SHOW THIS LOCATION IN ORDER TO | | | VERIFY GROUPING OF MAINS. | | | 215.5,230.72 , 230.70 | | | | | | 2)NOTE: PLEASE SEE AN EQUIPMENT | | | GROUNDING CONDUCTOR IS BEING SHOWN | | | BEFORE THE FIRST MEANS OF DISCONNECT | | | LOCATED AHEAD OF MAIN "B". | | | PLEASE SEE 250.6,250.24, ONLY AFTER THE | | | FIRST MEANS OF DISCONNETC. | | | | | | 3)NOTE: PLEASE SEE BLDG REVIEW COMMENTS | | | WITH RESPECT TO 3-STORY, AND HABITABLE | | | ROOM AT 3RD LEVEL. | | | PLEASE SEE ELECTRICAL PLANS MAY ONLY | | | INDICATE, SD, MEANS OF EGRESS LTS. | | | TV, PHONE, SINK, GFI'S, AND OTHER | | | ELECTRICAL RECEPTS ARE TO BE REMOVED. | | | A NOTE ON ELECTRICAL, WILL BE REQUIRED | | | TO STATE, " NON-HABITABLE ROOM" NOT FOR | | | HUMAN OCCUPANCY". | | | | | | FBC TABLE 500 | | | | | | 4)NOTE: PLEASE SEE REDLINED MIN | | | CLEARENCES FOR AHU DISC IN GARAGE. | | | 110.26 | | | | | | PLEASE MAKE THE ABOVE CORRECTIONS, AND | | | SUBMIT FOR REVIEW. IF THERE ARE ANY | | | QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|