Plan Review Notes
Plan Review Notes For Permit 05090701
Permit Number 05090701
Review Stop E
Sequence Number 2
Notes
Date Text
2005-12-09 00:00:00*** UNSAT ***
  
 PLEASE SEE TWO NOTES FROM PREVIOUS
 REVIEW AND NOTE DUE TO BLD REVIEW.
  
  
 1)NOTE: PLEASE SEE PLANS STILL INDICATE
 ONLY ONE DISCONNECT OUTSIDE NEXT TO
 METER, WHERE-AS RISER SHOWS TWO?
 PLEASE SHOW THIS LOCATION IN ORDER TO
 VERIFY GROUPING OF MAINS.
 215.5,230.72 , 230.70
  
 2)NOTE: PLEASE SEE AN EQUIPMENT
 GROUNDING CONDUCTOR IS BEING SHOWN
 BEFORE THE FIRST MEANS OF DISCONNECT
 LOCATED AHEAD OF MAIN "B".
 PLEASE SEE 250.6,250.24, ONLY AFTER THE
 FIRST MEANS OF DISCONNETC.
  
 3)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 WITH RESPECT TO 3-STORY, AND HABITABLE
 ROOM AT 3RD LEVEL.
 PLEASE SEE ELECTRICAL PLANS MAY ONLY
 INDICATE, SD, MEANS OF EGRESS LTS.
 TV, PHONE, SINK, GFI'S, AND OTHER
 ELECTRICAL RECEPTS ARE TO BE REMOVED.
 A NOTE ON ELECTRICAL, WILL BE REQUIRED
 TO STATE, " NON-HABITABLE ROOM" NOT FOR
 HUMAN OCCUPANCY".
  
 FBC TABLE 500
  
 4)NOTE: PLEASE SEE REDLINED MIN
 CLEARENCES FOR AHU DISC IN GARAGE.
 110.26
  
 PLEASE MAKE THE ABOVE CORRECTIONS, AND
 SUBMIT FOR REVIEW. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]