Plan Review Notes
Plan Review Notes For Permit 05090701
Permit Number 05090701
Review Stop M
Sequence Number 1
Notes
Date Text
2005-09-26 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE
 SIGNED.
 2) ENERGY CALCULATIONS CALLING FOR A 4
 TON A/C SYSTEM AND A 5 TON A/C SYSTEM,
 PLANS SHOWING TWO 5 TON A/C SYSTEMS.
 ENERGY CAL'S AND PLANS MUST COINCIDE.
 3) NEED MANUFACTURE'S INFO. REGUARDING
 MODEL NUMBER, TYPE OF GAS, AND BTU'S FOR
 VENTLESS FIREPLACE.
 4) NEED COMBUSTION AIC CALCULATIONS FOR
 VENTLESS FIREPLACE.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.