| 2005-09-23 00:00:00 | *********** UNSAT ********* |
| | |
| | 1)NOTE: PLEASE SEE 250.66,310.15B6 FOR |
| | MIN GROUNDING ELECTRODE CONDUCTOR FOR |
| | 400A SERVICE AS SHOWN. 1/0 MIN. |
| | |
| | 2)NOTE: PLEASE SEE 250.6,250.24, AN |
| | "EQUIPMENT GROUNDING CONDUCTOR" IS ONLY |
| | INSTALLED AFTER THE FIRST MEASN OF |
| | DISCONNECT(S). |
| | |
| | 3)NOTE: PLEASE SEE MISSING RECEPTS PER |
| | 210.52. PLEASE SEE MANY OF THESE ARE |
| | REDLINED ON ONE SET OF REVIEWED PLANS |
| | FOR LOCATIONS. |
| | |
| | 4)NOTE: PLEASE SEE MISSING BATH GFI PER |
| | 210.52D, 210.11C3, BATH #5. |
| | |
| | PLEASE ALSO VERIFY ONLY ONE CIRCUIT |
| | SHOWN FOR BATH GFI CIRCUIT.? |
| | 210.11C3. THIS IS ONLY A NOTE: |
| | |
| | 5)NOTE: PLEASE SEE A RECEPT IS SHOWN ON |
| | ELECTRICAL PLANS FOR WHIRLPOOLTUB, |
| | HOWEVER THIS DEDICATED CIRCUIT IS NOT |
| | INDICATED ON PANEL SCHEDULE OR IN LOAD |
| | CALCULATIONS. |
| | PLEASE ALSO SEE MISSING INDICATION OF |
| | GFI PROTECTION PER 680.71 |
| | 215.5, 220 |
| | |
| | 6)NOTE: PLEASE SEE 210.8A2, WHICH |
| | REQUIRES ALL RECEPTS IN GARAGE NOT USED |
| | FOR A DEDICATED CIRCUIT, SHALL BE GFI. |
| | PLEASE ALSO SEE 210.8A7 FOR ALL RECEPTS |
| | OF WET BARS/ SINKS (NOT KITCHEN) TO BE |
| | GFI OR GFI PROTECTED. |
| | PLEASE SEE RECEPT W/IN 6' OF SINK IN |
| | OBSERVATION ROOM, THIRD LEVEL. |
| | |
| | 7)NOTE: PLEASE SEE PLANS INDICATE ONLY |
| | ONE MAIN DISCONNECT AT METER LOCATIION |
| | ON OUTSIDE OF HOUSE, WHERE-AS RISER |
| | INDICATES , TWO MAINS. |
| | PLEAS ADJUST. |
| | |
| | 8)NOTE: PLEASE INDICATE CONTINUOUS LOADS |
| | IN LOAD CALCUALTIONS ON PANEL "B" FOR |
| | POOL PUMP AND POOL HEATER. 215.3,230.42. |
| | THESE LOADS SHOULD BE 125% MIN. |
| | PLEASE ADJUST LOAD CALCS. |
| | |
| | 9)NOTE: PLEASE SEE DISCONNECTING MEANS |
| | FOR AHU ON SECOND FLR TO MEET 110.26 OR |
| | IS PART OF UNIT? |
| | ** ONLY A NOTE** |
| | PLEASE SEE DISCONNECTING MEANS FOR AHU |
| | IN GARAGE TO MEET 110.26, IF INSTALLED. |
| | |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO TWO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE COPY OF ANY OLD/VOIDED SHEETS SHOULD |
| | BE SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABVOE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |