Plan Review Notes
Plan Review Notes For Permit 05090701
Permit Number 05090701
Review Stop E
Sequence Number 1
Notes
Date Text
2005-09-23 00:00:00*********** UNSAT *********
  
 1)NOTE: PLEASE SEE 250.66,310.15B6 FOR
 MIN GROUNDING ELECTRODE CONDUCTOR FOR
 400A SERVICE AS SHOWN. 1/0 MIN.
  
 2)NOTE: PLEASE SEE 250.6,250.24, AN
 "EQUIPMENT GROUNDING CONDUCTOR" IS ONLY
 INSTALLED AFTER THE FIRST MEASN OF
 DISCONNECT(S).
  
 3)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52. PLEASE SEE MANY OF THESE ARE
 REDLINED ON ONE SET OF REVIEWED PLANS
 FOR LOCATIONS.
  
 4)NOTE: PLEASE SEE MISSING BATH GFI PER
 210.52D, 210.11C3, BATH #5.
  
 PLEASE ALSO VERIFY ONLY ONE CIRCUIT
 SHOWN FOR BATH GFI CIRCUIT.?
 210.11C3. THIS IS ONLY A NOTE:
  
 5)NOTE: PLEASE SEE A RECEPT IS SHOWN ON
 ELECTRICAL PLANS FOR WHIRLPOOLTUB,
 HOWEVER THIS DEDICATED CIRCUIT IS NOT
 INDICATED ON PANEL SCHEDULE OR IN LOAD
 CALCULATIONS.
 PLEASE ALSO SEE MISSING INDICATION OF
 GFI PROTECTION PER 680.71
 215.5, 220
  
 6)NOTE: PLEASE SEE 210.8A2, WHICH
 REQUIRES ALL RECEPTS IN GARAGE NOT USED
 FOR A DEDICATED CIRCUIT, SHALL BE GFI.
 PLEASE ALSO SEE 210.8A7 FOR ALL RECEPTS
 OF WET BARS/ SINKS (NOT KITCHEN) TO BE
 GFI OR GFI PROTECTED.
 PLEASE SEE RECEPT W/IN 6' OF SINK IN
 OBSERVATION ROOM, THIRD LEVEL.
  
 7)NOTE: PLEASE SEE PLANS INDICATE ONLY
 ONE MAIN DISCONNECT AT METER LOCATIION
 ON OUTSIDE OF HOUSE, WHERE-AS RISER
 INDICATES , TWO MAINS.
 PLEAS ADJUST.
  
 8)NOTE: PLEASE INDICATE CONTINUOUS LOADS
 IN LOAD CALCUALTIONS ON PANEL "B" FOR
 POOL PUMP AND POOL HEATER. 215.3,230.42.
 THESE LOADS SHOULD BE 125% MIN.
 PLEASE ADJUST LOAD CALCS.
  
 9)NOTE: PLEASE SEE DISCONNECTING MEANS
 FOR AHU ON SECOND FLR TO MEET 110.26 OR
 IS PART OF UNIT?
 ** ONLY A NOTE**
 PLEASE SEE DISCONNECTING MEANS FOR AHU
 IN GARAGE TO MEET 110.26, IF INSTALLED.
  
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE COPY OF ANY OLD/VOIDED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABVOE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  