| Plan Review Notes For Permit 05090679 |
| Permit Number |
05090679 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-11-22 00:00:00 | | | | THE COMMENTS FOR THIS REVIEW ARE THE | | | SAME AS THE LAST REVIEW. | | | | | | THE ENGINEER OF RECORD NEEDS TO INDICATE | | | IF THE "PANEL" SHOWN ON SHEET 2 OF 3 | | | ELECTRICAL SCHEMATIC IS NEW OR EXISTING. | | | IF IT IS NEW PLEASE SUBMIT DETAILS FOR | | | THE PANEL SHOWN ON THE SCHEMATIC, FEEDER | | | AND CONDUIT SIZE AND TYPE, PANEL RATING | | | AND OCP, PANEL SCHEDULE AND COMPUTED | | | LOAD. | | | | | | MR KOVNER NEEDS TO CALL ME REGARDING | | | THIS MATTER IF THERE ARE ANY QUESTIONS. | | | | | | ALSO THE ELECTRICAL CONTRACTOR | | | SUBMITTING THE PANEL SCHEDULE HAS AN | | | INCORRECT ADDRESS. THE PANEL SCHEDULE | | | ALONE DOES NOT RESPOND TO ALL OF THE | | | COMMENT. FEEDER CONDUIT AND CONDUCTOR | | | SIZES ARE NOT ADDRESSED, AND MAY NOT | | | NEED TO BE IF THE PANEL ON THE SCHEMATIC | | | IS EXISTING, ONE OF THE ISSUES THE | | | ENGINEER OF RECORD HAS NOT CORRECTED. | | | | | | DO NOT RESUBMIT WITHOUT A CORRECTED | | | WIRING SCHEMATIC. SEE FLORIDA STATUTE | | | 553.80, ATTACHED. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | |
|