| 2005-09-23 00:00:00 | | | | THE ENGINEER OF RECORD NEEDS TO INDICATE | | | IF THE "PANEL" SHOWN ON SHEET 2 OF 3 | | | ELECTRICAL SCHEMATIC IS NEW OR EXISTING. | | | IF IT IS NEW PLEASE SUBMIT DETAILS FOR | | | THE PANEL SHOWN ON THE SCHEMATIC, FEEDER | | | AND CONDUIT SIZE AND TYPE, PANEL RATING | | | AND OCP, PANEL SCHEDULE AND COMPUTED | | | LOAD. | | | | | | MR KOVNER NEEDS TO CALL ME REGARDING | | | THIS MATTER IF THERE ARE ANY QUESTIONS. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|