| 2005-09-23 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} EQUIPMENT GROUNDING CONDUCTORS PER | | | 250.122 ARE REQUIRED FROM THE MAIN TO | | | THE SUB PANELS. | | | | | | 2} PLEASE NOTE THE OCP LISTED ON PANEL | | | SCHEDULE "B" DOES NOT CORRELATE WITH THE | | | LOAD FOR THE WHIRLPOOL. | | | | | | 3} A SMOKE DETECTOR IS REQUIRED IN CLOSE | | | PROXIMITY OF THE STAIRS ON THE 1ST FLOOR | | | PER 905.2.2 FBC. | | | | | | 4} BATH #2 IS REQUIRED TO HAVE A | | | RECEPTACLE PER 210.52(D), ON A 20 AMP | | | CIRCUIT PER 210.11(C)(3), GFI PROTECTED | | | PER 210.8(A)(1). | | | | | | 5} THE WHIRLPOOL IS REQUIRED TO BE GFI | | | PROTECTED PER 680.71. PLEASE SHOW ON THE | | | PLAN. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | |
|