Plan Review Notes
Plan Review Notes For Permit 05090674
Permit Number 05090674
Review Stop E
Sequence Number 1
Notes
Date Text
2005-09-23 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} EQUIPMENT GROUNDING CONDUCTORS PER
 250.122 ARE REQUIRED FROM THE MAIN TO
 THE SUB PANELS.
  
 2} PLEASE NOTE THE OCP LISTED ON PANEL
 SCHEDULE "B" DOES NOT CORRELATE WITH THE
 LOAD FOR THE WHIRLPOOL.
  
 3} A SMOKE DETECTOR IS REQUIRED IN CLOSE
 PROXIMITY OF THE STAIRS ON THE 1ST FLOOR
 PER 905.2.2 FBC.
  
 4} BATH #2 IS REQUIRED TO HAVE A
 RECEPTACLE PER 210.52(D), ON A 20 AMP
 CIRCUIT PER 210.11(C)(3), GFI PROTECTED
 PER 210.8(A)(1).
  
 5} THE WHIRLPOOL IS REQUIRED TO BE GFI
 PROTECTED PER 680.71. PLEASE SHOW ON THE
 PLAN.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  