| 2005-09-19 00:00:00 | ********* UNSAT ********** | | | | | | 1)NOTE: PLEASE SHOW CIRCUITING ON PLANS | | | AND CORRELATE WITH THE SUBMITTED PANEL | | | SCHEDULES FOR NEW ELECTRICAL. | | | PLEASE SEE PANEL "A" STILL APPEARS TO BE | | | SHOWN FACING INTO OTHER TENANT SPACE? | | | PLEASE SEE 240.24 (A)(B). | | | | | | 2)NOTE: PLEASE CORRELATE ELECTRICAL | | | FLOOR PLAN WITH A-SHEETS, PLEASE SEE | | | AREA WITH WHAT APPEARS TO CONTAIN EXIT | | | LTS WITH-OUT GOING TO ANYWHERE? | | | PLEASE SEE | | | PLEASE SEE FIRE REVIEW COMMENTS FOR EXT | | | LTS AND EM LTS TO BE ADJUSTED OR MOVED. | | | NFPA-101. 7.8,7.9, PLEASE ALSO INDICATE | | | CIRCUITING PER 700.12E TO LOCAL BRANCH | | | CIRCUIT IN AREA | | | | | | 3)NOTE: PLEASE VERIFY NEW OR EXISTING | | | SIGN CIRCUIT REQUIRED FOR EACH. 600.5 | | | PLEASE INDICATEWHERE ENTRANCED IS | | | LOCATED , INTERIOR HALL? EXTERIOR? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|