| Plan Review Notes For Permit 05090663 |
| Permit Number |
05090663 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-10-14 00:00:00 | *** UNSAT *** | | | | | | 1)NOTE: PLEASE SEE THAT IS DOES NOT | | | APPEAR COMMENTS FROM PREVIOUS REVIEW BY | | | FIRE MARSHAL'S OFFICE HAVE BEEN | | | ADDRESSED. | | | PLEASE SEE ELECTRICAL PLANS DO NOT | | | INDICATE THE REQUUIRED EITHER NEW OR | | | EXISTING EMERGENCY OR EXIT LTS AS | | | REQUESTED. | | | PLEASE SEE NFPA 101 7.8,7.9 AND NFAP 70 | | | 700.12E FOR CIRCUITING. | | | | | | PLEASE SEE FIRE REVIEWERS COMMENT IN | | | REFERENCE TO PULL STATIONS ETC. | | | | | | PLEASE SEE THESE WILL DIRECTLY AFFECT | | | ELECTRICAL PLANS. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|