| Plan Review Notes For Permit 05090663 |
| Permit Number |
05090663 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-09-23 00:00:00 | ******DENIED****** | | | | | | 1) PLANTERS SHALL NOT BE ARRANGED WHERE | | | INTERFERENCE WITH EXITING REQUIREMENTS | | | MAY OCCUR. | | | | | | 2) NO MENTION OF EXIT SIGNS/EMERGENCY | | | LIGHTS. NEW OR EXISTING? | | | | | | 3) PLANS SHOW THE RELOCATION OF A PULL | | | BOX AND STROBE. IS THERE AN EXISTING | | | FIRE ALARM SYSTEM? PLEASE EXPLAIN | | | LOCATION OF PULL BOX AWAY FROM MAIN | | | EXIT? | | | | | | 4) PLANS MENTION FIRE EXTINGUISHERS. | | | 2A-10 B,C RATED EXTINGUISHERS ARE | | | REQUIRED AND SHALL BE MOUNTED TO SATISFY | | | THE 75' TRAVEL DISTANCE BASED ON LOW | | | HAZARD. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|