Plan Review Notes
Plan Review Notes For Permit 05090647
Permit Number 05090647
Review Stop B
Sequence Number 1
Notes
Date Text
2005-11-08 00:00:00****CORRECTIONS****
 05090646 AND 05090647
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)UNDER WHICH CODE HAS THIS PROJECT
 BEEN DESIGNED?FBC2001 OR FBC2004?
 SPECIFY ON THE PLAN.THIS COMMENT LIST
 CANNOT REFER TO SPECIFIC CODE SECTIONS
 AS THIS HAS NOT YET BEEN DETERMINED.
  
 3.)THE FIRE PROTECTION SYSTEM IS TO BE
 DESIGNED BY A FIRE PROTECTION SYSTEM
 DESIGNER, FS553.79(6)(C), FAC61G15-32.
 SOMEONE HAS WRITTEN ?PRE ENGINEERED? ON
 THE SPECIFICATION SHEETS, AND MADE
 REFERENCE TO UL1245.THIS IS A TEST
 STANDARD, NOT A LISTING.ONE SET HAS
 BEEN RETAINED.
  
 4.)THE SITE PLAN IS NOT CLEAR.IS
 THE PAINT SPRAY BOOTH INSIDE OF THE
 BUILDING?THE ORIGINAL SITE PLAN HAS
 BEEN ALTERED.IF IT IS OUTSIDE, PROVIDE
 WIND DESIGN AND ANCHORING INFORMATION
 FBC16.
  
 5.)PROVIDE INFORMATION IN REGARDS TO
 THE BOOTH.CONSTRUCTION MATERIALS,
 CONNECTIONS, ETC.
  
 6.)DECLARE OCCUPANCY FOR THE EXISTING
 STRUCTURES, THE PREP STATION AND THE
 PAINT BOOTH.FBC3.SHOW OCCUPANCY
 SEPARATION IF APPLICABLE.
  
 7.)WHERE IS THE PAINT STORED?PROVIDE
 GALLONS, TYPE, ETC. TO ASSIST IN
 DETERMINING OCCUPANCY, SEE H AND S
 OCCUPANCIES.
  
 8.)ARE YOU USING LP OR NATURAL GAS?
 BOTH ARE SHOWN ON THE PLAN.WHAT IS
 THIS FOR?
  
 9.)SHEET 2 OF 6, PLAN VIEW, REFERS TO
 CLASSES AND DIVISIONS.WHAT IS THE CODE
 REFERENCE FOR THIS?INFORMATION ON THE
 PLAN IS TO BE SPECIFIC, AND CANNOT REFER
 TO CODE ONLY, ESPECIALLY CODES WHICH ARE
 NOT GOVERNING CODE FOR THIS PROJECT, FBC
 CHAPTER 1.
  
 10.)THE PRINTED NAME AND LICENSE
 NUMBER OF THE PERSON SEALING THE PLAN IS
 TO BE ON THE DOCUMENT, FAC61G15-23.002.
  
 11.)PROVIDE A PENETRATION DETAIL FOR
 THE EXHAUST AND INTAKE.
  
 12.)THE CONNECTIONS FOR THE PLENUM,
 SHEET 3, IS TO BE DONE ?BY OTHERS?.
 PROVIDE A DETAIL.
  
 13.)SHOW THE DOOR DIMENSION, FBC10.
  
 14.)A PLAN WAS SHOWN FOR THE PAINT
 BOOTH, BUT NOT FOR THE PREP STATION.IT
 APPEARS THAT ONE SIDE OF THE PREP
 STATION IS OPEN, IS THAT CORRECT?IF
 NOT, SHOW EXIT DOOR ON THE PLAN.
  
 15.)SHOW EXITING INFORMATION, SEE
 FBC10.
  
 NOTE ? NOT ENOUGH INFORMATION ON THE
 PLAN TO DETERMINE CODE COMPLIANCE.
  