Plan Review Notes For Permit 05090646
Permit Number 05090646
Review Stop B
Sequence Number 2
Notes
Date Text
2005-12-22 00:00:00****CORRECTIONS****
 05090646 AND 05090647
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 PREVIOUS CORRECTION LIST; NUMBERING TO
 REMAIN THE SAME FOR CONSISTENCY
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 REQUIRED BEFORE THE PERMIT CAN BE
 ISSUED.
  
 2.)UNDER WHICH CODE HAS THIS PROJECT
 BEEN DESIGNED?FBC2001 OR FBC2004?
 SPECIFY ON THE PLAN.THIS COMMENT LIST
 CANNOT REFER TO SPECIFIC CODE SECTIONS
 AS THIS HAS NOT YET BEEN DETERMINED.
  
 FBC2000 WAS HAND WRITTEN ON THE PLAN,
 SHEET 2. THIS IS NOT A VALID GOVERNING
 CODE. SHEET 5 HAS FBC2004 HAND WRITTEN.
 ANY CHANGES TO THE PLAN ARE TO BE DONE
 BY THE ENGINEER.IF CHANGES ARE
 HANDWRITTEN, THEY ARE TO BE INITIALED.
 AS IT APPEARS THAT CHANGES MAY HAVE BEEN
 DONE BY SOMEONE OTHER THAN MR. MOLYET,
 PE, I WOULD LIKE CONFIRMATION EITHER BY
 SIGNED AND SEALED LETTER THAT HAND
 WRITTEN CHANGES WERE DONE BY HIM, OR
 HAVE THE CHANGES IMPLEMENTED INTO THE
 PLAN AND NEW SHEETS PRINTED.
  
 IT IS STILL UNCLEAR AS TO WHICH CODE THE
 ENGINEER HAS DESIGNED TO.
  
 3.)THE FIRE PROTECTION SYSTEM IS TO BE
 DESIGNED BY A FIRE PROTECTION SYSTEM
 DESIGNER, FS553.79(6)(C), FAC61G15-32.
 SOMEONE HAS WRITTEN "PRE ENGINEERED" ON
 THE SPECIFICATION SHEETS, AND MADE
 REFERENCE TO UL1245.THIS IS A TEST
 STANDARD, NOT A LISTING.ONE SET HAS
 BEEN RETAINED.
  
 NOT ADDRESSED.SAME PLANS SUBMITTED.
 THE WORDS "PYRO-CHEM IS THE DESIGNER FOR
 A PRE-ENGINEERED FIRE SYSTEM - UL 1254
 IS THE LISTING" WAS WRITTEN ON THE SAME
 UNSEALED PLAN.IF PYRO-CHEM IS LICENSED
 TO BE A FIRE PROTECTION SYSTEM DESIGNER,
 PROVIDE PLANS IN COMPLIANCE - SIGNED,
 SEALED, TITLE BLOCK.SEE FAC61G15-23,
 FAC615-32.PLEASE CONTACT FBPE IF THE
 DESIGN PROFESSIONAL IS UNCLEAR AS TO HIS
 OR HER RESPONSIBILITIES.
  
 4.)THE SITE PLAN IS NOT CLEAR.IS
 THE PAINT SPRAY BOOTH INSIDE OF THE
 BUILDING?THE ORIGINAL SITE PLAN HAS
 BEEN ALTERED.IF IT IS OUTSIDE, PROVIDE
 WIND DESIGN AND ANCHORING INFORMATION
 FBC16.
  
 PROVIDE A SITE PLAN PREPARED BY DESIGNER
 OF RECORD AS THE SITE PLAN ADDRESSES
 CODE COMPLIANCE ISSUES.
  
 5.)PROVIDE INFORMATION IN REGARDS TO
 THE BOOTH.CONSTRUCTION MATERIALS,
 CONNECTIONS, ETC.
  
 DESIGNER OF RECORD IS TO PROVIDE DESIGN
 CRITERIA ON THE PLAN.THE ASSEMBLY
 INSTRUCTIONS ARE NOT REQUIRED TO BE A
 PART OF THE PERMIT PACKAGE.HAVE THE
 ENGINEER PROVIDE INFORMATION REQUESTED.
  
 6.)DECLARE OCCUPANCY FOR THE EXISTING
 STRUCTURES, THE PREP STATION AND THE
 PAINT BOOTH.FBC3.SHOW OCCUPANCY
 SEPARATION IF APPLICABLE.
  
 NOT ADDRESSED."ONE MAN IN PAINT BOOTH"
 IS NOT AN OCCUPANCY.IF THE ENGINEER IS
 UNCLEAR AS TO HOW TO DECLARE AN
 OCCUPANCY AND SHOW SEPARATIONS AS
 REQUESTED, PLEASE HAVE HIM CONTACT ME.
  
 7.)WHERE IS THE PAINT STORED?PROVIDE
 GALLONS, TYPE, ETC. TO ASSIST IN
 DETERMINING OCCUPANCY, SEE H AND S
 OCCUPANCIES.
  
 NOT ADDRESSED.
  
 8.)ARE YOU USING LP OR NATURAL GAS?
 BOTH ARE SHOWN ON THE PLAN.WHAT IS
 THIS FOR?
  
 THERE IS A NOTE (WHICH IS NOT INITIALED
 AS REQUIRED) WHICH INDICATES THAT THIS
 WILL BE NATURAL GAS.WHAT IS THIS FOR?
  
 9.)SHEET 2 OF 6, PLAN VIEW, REFERS TO
 CLASSES AND DIVISIONS.WHAT IS THE CODE
 REFERENCE FOR THIS?INFORMATION ON THE
 PLAN IS TO BE SPECIFIC, AND CANNOT REFER
 TO CODE ONLY, ESPECIALLY CODES WHICH ARE
 NOT GOVERNING CODE FOR THIS PROJECT, FBC
 CHAPTER 1.
  
 NOT ADDRESSED.
  
 10.)THE PRINTED NAME AND LICENSE
 NUMBER OF THE PERSON SEALING THE PLAN IS
 TO BE ON THE DOCUMENT, FAC61G15-23.002.
  
 PROVIDE A TITLE BLOCK WITH ALL
 INFORMATION REQUIRED BY FAC61G15-23.002.
  
 11.)PROVIDE A PENETRATION DETAIL FOR
 THE EXHAUST AND INTAKE.
  
 NOT ADDRESSED.
  
 12.)THE CONNECTIONS FOR THE PLENUM,
 SHEET 3, IS TO BE DONE "BY OTHERS".
 PROVIDE A DETAIL.
  
 ENGINEER CANNOT ADDRESS THIS STRUCTURAL
 ITEM WITH A SHOP DRAWING.INCORPORATE
 INTO THE PLAN OR PROVIDE A TITLE BLOCK,
 SIGN AND SEAL THE DRAWING WHICH WAS
 STAPLED TO THE PLAN.
  
 13.)SHOW THE DOOR DIMENSION, FBC10.
  
 CHANGES TO THE PLAN ARE TO BE INITIALED
 OR INCORPORATED INTO THE PLAN.
  
 14.)A PLAN WAS SHOWN FOR THE PAINT
 BOOTH, BUT NOT FOR THE PREP STATION.IT
 APPEARS THAT ONE SIDE OF THE PREP
 STATION IS OPEN, IS THAT CORRECT?IF
 NOT, SHOW EXIT DOOR ON THE PLAN.
  
 SHEET 2 SHOWS DOORS WHICH DO NOT APPEAR
 TO BE COMPLIANT WITH FBC11-4.13.PLAN
 VIEW HAS AN ACCESS DOOR HAND DRAWN.IT
 APPEARS THAT THERE ARE FOLDING DOORS IN
 THE FRONT, BUT THE PLAN VIEW DOES NOT
 CORRELAT WITH THE FRONT VIEW.THERE ARE
 TWO PLAN VIEWS, BOTH REFER TO THE SPRAY
 BOOTH.PROVIDE FLOOR PLANS FOR THE PREP
 STATION AND THE PAINT BOOTH, CLEARLY
 SHOW DOORS, SO THAT CODE COMPLIANCE (FBC
 CHAPTER 10 AND FBC CHAPTER 11) CAN BE
 DETERMINED.
  
 15.)SHOW EXITING INFORMATION, SEE
 FBC10.
  
 NOT ADDRESSED.ENGINEER IS TO PROVIDE A
 CLEAR SITE PLAN, A FLOOR PLAN OF THE
 EXISTING, SHOW THE PROPOSED
 IMPROVEMENTS, AND A LIFE SAFETY PLAN.
  
 NOTE - NOT ENOUGH INFORMATION ON THE
 PLAN TO DETERMINE CODE COMPLIANCE.
  
  
 NEW COMMENT -
  
 16.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW FEE WILL BE CHARGED IF
 COMMENTS ARE NOT PROPERLY ADDRESSED IN
 THE THIRD REVIEW.