Plan Review Notes
Plan Review Notes For Permit 05090645
Permit Number 05090645
Review Stop B
Sequence Number 1
Notes
Date Text
2005-10-13 00:00:00 
  
 1) 424.2.17.1 OUTDOOR SWIMMING POOLS.
 OUTDOOR SWIMMING POOLS SHALL BE PROVIDED
 WITH A BARRIER COMPLYING WITH
 424.2.17.1.1 THROUGH 424.2.17.1.14.
  
 424.2.17.1.5 CHILD SAFETY BARRIER
 ASTM D5034 100 LB TENSILE STRNGTH
 ASTM D3787 150 LB BALL BURST
 STRENGTH
  
 2) 13-612.1.ABC.2.3.2 COVERS REQUIRED.
 SPAS AND HEATED SWIMMING POOLS SHALL BE
 EQUIPPED WITH A COVER DESIGNED TO
 MINIMIZE HEAT LOSS.
  
 3) FBC.2328.2 FENCES NOT EXCEEDING 6
 FEETIN HEIGHT, SHALL BE CONSTRUCTED TO
 MEET THE FOLLOWING MINIMUM REQUIREMENTS:
 FROM NOMINAL 4 X 4 X 8 LONG POSTS NO.2
 GRADE OR BETTER SPACED 4 FEETON
 CENTER, AND EMBEDDED 2 FEETINTO A
 CONCRETE FOOTING 10 INCHES IN DIAMETER
 AND 2 FEETDEEP.
  
 4) FBC.2328.3 FENCES NOT EXCEEDING 5
 FEETOR 4 FEET IN HEIGHT SHALL BE
 CONSTRUCTED AS PROVIDED IN FBC.2328.2,
 EXCEPT THAT THE SPACING OF POSTS MAY BE
 INCREASED TO 5 FEETAND 6 FEETON
 CENTER FOR THESE HEIGHTS, RESPECTIVELY.
 PLEASE STATE THE TYPE/HEIGHT OF
 FENCE,AND THE TYPES OF SAFETY DEVICES
 INSTALL AT THIS LOCATION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561) 805-6726
 FAX(561) 659-8O26
 [email protected].
  
  