| 2005-09-14 00:00:00 | DENIED | | | | | | 1) SPECIFY THE MEAN ROOF HEIGHT OF THE | | | STRUCTURE AND THE PITCH OF THE SLOPED | | | ROOF. SPECIFY THE TYPE AND NUMBER OF | | | FASTENERS IF MECHANICALLY FASTENED OR | | | THE TYPE OF ADHESIVE THAT WILL BE USED | | | FOR THE TILE. | | | | | | 2) THE FLORIDA COVER SHEET FOR THE | | | MONIER LIFETILE FL560-R1 IS VALIDATED | | | BUT HAS NOT BEEN APPROVED. | | | | | | 3) THE PRODUCT EVALUATION LISTED WITH | | | THE STATE FOR THE MONIER BARREL CONCRETE | | | TILE IS SBCCI. SUBMIT THE REPORT THAT | | | CORRESPONDS WITH THE FL#. A MIAMI DADE | | | NOA WAS SUBMITTED. | | | | | | 4) SPECIFY THE APPROVED ASSEMBLY FROM | | | FROM PAGES 6-43 OF THE PRODUCT APPROVAL | | | FOR THE POLYGLASS MODIFIED ROOFING | | | SYSTEMS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|