2006-01-31 00:00:00DENIED
 2ND REVIEW
  
 1) LETTER OF INTENT IS REQUIRED TO HAVE
 THE WET SIGNATURE, DATE AND EMBOSSED
 SEAL OF THE ENGINEER.
  
 2) THE DESIGN PRESSURES LISTED ON THE
 ENGINEERING FOR THE BUTT GLASS ASSEMBLY
 DO NOT MEET THE REQUIRED WINDLOAD
 PRESSURES FOR THE OPENING AS SPECIFIED
 ON THE APPROVED PLANS FOR THE STRUCTURE.
 THE PLANS SPECIFY +33.7 AND -44.0 PSF.
 SEE COMMENT #2 OF FIRST REVIEW.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  