Plan Review Notes
Plan Review Notes For Permit 05090596
Permit Number 05090596
Review Stop B
Sequence Number 1
Notes
Date Text
2005-10-18 00:00:00DENIED
  
 - BUTT GLAZING
 - CODE REFERENCES
 2001 FBC 2406.2
 2001 FBC 103.7.1
 2001 FBC 104.2.1.2
  
 1) THE INCORRECT ADDRESS IS SPECIFIED ON
 THE SUBMITTED DOCUMENTS. THE CORRECT
 ADDRESS IS 1343 N. MANGONIA DRIVE.
  
 2) THE SPECIFIED DESIGN PRESSURES ARE
 TOO LOW. THE REQUIRED PRESSURES LISTED
 ON THE STRUCTURES PLANS ARE +33.7 AND
 -44.0 PSF.
  
 3) SUBMIT SIGNED AND SEALED CLACULATIONS
 FOR THE GLASS STRENGTH AND DEFLECTION OF
 NO MORE THAN 0.16". PROVIDE CALCULATIONS
 INDICATING THE REQUIRED GE 1200 SILICONE
 BEAD SIZE.
  
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION INSTRUCTIONS FOR THE GE
 1200 SILICONE STRUCTURAL SEALANT.
  
 5) THE PRODUCT APPROVALS FOR THE ARCH
 ALUMINUM STOREFRONT SYSTEM IS FOR A
 STRAIGHT INLINE APPLICATION WITH MULLS
 BETWEEN THE GLAZED PANELS. THE SUBMITTAL
 IS HAS THE FRAMES AT ANGLES AND NO MULLS
 BETWEEN THE PANELS. THEREFORE, THE FRAME
 IS BEING USED OUTSIDE OF THE SCOPE OF
 THE PRODUCT APPROVAL. SUBMIT AN ANALYSIS
 BASED ON TESTING OR CALCULATIONS FOR THE
 FRAME. PROVIDE ATTACHMENT DETAILS FOR
 THE FRAMES TO THE STRUCTURE.
  
 6) BEFORE THE PERMIT IS ISSUED A SIGNED
 SEALED AND DATED LETTER FROM THE
 ENGINEER STATING THAT HE WILL INSPECT
 THE INSTALLATION FOR COMPLIANCE WITH HIS
 DESIGN IS REQUIRED.
  
 7) PRIOR TO RECEIVING A CERTIFICATE OF
 OCCUPANCY FOR THE JOB, A SIGNED, SEALED
 AND DATED LETTER FROM THE ENGINEER MUST
 BE SUBMITTED CERTIFYING THAT THE PRODUCT
 WAS CONSTRUCTED AND INSTALLED ACCORDING
 THE DESIGN SPECIFICATIONS THAT WERE
 SUBMITTED.
  
 8) THE VALUE OF THE WORK LISTED ON THE
 APPLICATION IS IN ERROR. IT APPEARS TO
 BE THE VALUE OF THE STRUCTURE. THE COST
 OF THE SCOPE OF WORK FOR THIS PERMIT IS
 LIMITED TO THE LABOR AND MATERIAL COSTS
 FOR THE BUTT GLASS SYSTEM. REVISE THE
 AMOUNT LISTED ON THE APPLICATION AND
 HAVE THE PERMIT SUPERVISOR CORRECT THE
 PERMIT FEES ACCORDINGLY.
  