Plan Review Notes
Plan Review Notes For Permit 05090590
Permit Number 05090590
Review Stop E
Sequence Number 1
Notes
Date Text
2005-10-06 00:00:00*********** UNSAT *************
  
 ***** PROJECT ONLY/ PLAN REVIEW ONLY.
  
  
 1)NOTE: PLEASE KNOW, PLANS HAVE ONLY
 BEEN SUBMITTED FOR "PLAN REVIEW" AND
 WERE NOT SUBMITTED FOR PERMIT WITH FEES
 PAID BEFORE OCT 1ST, 2005.
 PLEASE SEE PLANS REFERENCE 2001 FBC FOR
 DESIGN ETC.
 PLEASE SEE ELECTRICAL, BLDG, MECH, FIRE
 , PLUMB PLANS WILL ALL BE REQUIRED TO
 CHANGED TO BE DESIGNED UNDER THE 2004
 FBC.
 PLEASE COMMENTS FROM OTHER REVIEWERS.
  
 2)NOTE: PLEASE SUBMIT ALL MANUFACTURE
 SPECS/CUT SHEETS FOR FIRE PUMP AND FIRE
 PUMP CONTROLLER. PLEASE INDICATE LOCKED
 ROTOR OCP PER 695.4B1. PLEASE SEE PLANS
 REF 695.5B
 PLEASE BE SURE ALL SPECS AND PLANS
 INDICATE THE MANUAL MEANS OF DISCONNECT
 LOCATED ON THE OUTSIDE OF THE EQUIPMENT
 AS REQUIRED PER 230.76,230.79, NFPA-101,
 10.4.2.
 PLEASE INCLUDE VOLTAGE PROPOSED FOR FIRE
 PUMP.
 PLEASE KNOW, EVEN THOUGH PLANS REFERENCE
 "BY OTHERS", THIS INFORMATION IS STILL
 REQUIRED WITH MAIN BLDG PLANS.
 UNABLE TO VERIFY CODE COMPLIANCE AT THIS
 TIME.
  
 3)NOTE: PELASE PROVIDE WIND LOADING
 CALCULATIONS FOR SITE LIGHTING POLES
 INCLUDING FIXTURES BEING ATTACHED.
 PLEASE ALSO PROVIDE POLE DETAIL WITH
 FIXTURE, FOUNDATION ETC.
 PLEASE KNOW, THE CALCUALTIONS WILL BE
 REVIEWED BY THE STRUCTUAL REVIEWER AND
 WILL BE REQUIRED TO MEET FBC 140MPH MIN.
  
 4)NOTE: PLEASE SEE 110.26 FOR MIN
 CLEARENCE REQUIRED FOR TRANSFORMER.
 FLOOR PLAN APPEARS TO SHOW TRANSFORMER
 LOCATED IN FRONT OF PANELS.
 IT SEEM THIS WILL BE MOUNTED ABOVE,
 HOWEVER RISER DIAGRAM DOES NOT REFLECT
 THIS.
 IF MOUNTED ABOVE, PLEASE PROVIDE A
 STRUCTUAL DETAIL FOR THIS.
  
 5)NOTE: PLEASE PROVIDE MIN SIZE FOR
 GUTTER ON RISER. PLEASE SEE FBC 104.2.1,
 CODES SHALL NOT BE REFERENCED IN WHOLE
 OR IN PART IN LEIU OF SPECIFIC
 DETAIL,INFORMATION ETC.
  
 6)NOTE: PLEASE SEE GROUNDING ELECTRODE
 SYSTEM IS ALSO REQUIRED TO BE ATTACHED
 TO FOOTER STEEL AND COLD WATER PIPE (IF
 METAL). PLEASE INLCUDE THESE ON
 GROUNDING DETAIL.250.50
 PLEASE ALSO SEE OTHER PIPING SYSTEMS TO
 BE BONDED. (FIRE SPRINKLER ETC)
 250.104
  
 ***** PLEASE SEE NOTE NUMBER ONE, PLANS
 WERE NOT SUBMITTED FOR PERMIT UNDER THE
 2001 FBC.
  
 *** PLEASE SEE ANY POSSIBLE COMMENTS
 FROM OTHER REVIEWERS WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-10-05 00:00:00IN ELEC FOR REVIEW.