Plan Review Notes
Plan Review Notes For Permit 05090590
Permit Number 05090590
Review Stop B
Sequence Number 1
Notes
Date Text
2006-01-30 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05090590
 ADD: 5563 45TH ST
 CONT:"PLAN REVIEW"
 PREMIER COMMERCIAL REALITY
 ANDY PRIBYL
 TEL: (954)214-4039
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 *****NOTE*****
 THIS PLAN WILL BE REVIEWED UNDER THE
 2004 FBC. PLANS HAD TO BE IN UNDER A
 PERMIT APPLICATION BEFORE OCT. 1,2005
 TO BE REVIWED UNDER THE 2001 FBC, NOT A
 PLAN REVIEW!!!!!!!!
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) CONTACT LILI URSA @ (561)822-1239
 FOR VALIDATION OF STREET NAME AND FOR
 ADDRESS ASSIGNMENT. THE PROPOSED STREET
 NAME IS NOT FOUND IN THE CITIES MASTER
 SREET ADDRESS GUIDE. PALM BEACH COUNTY
 PROPERTY APPRAISERS INDICATES (2) LOTS
 THAT WILL REQUIRE A UNITY OF TITLE
 BETWEEN THE LOTS FOR TABLE 601 ISSUES.
 THE PLAN REVIEW APPLICATION INDICATES
 THE ADDRESS AS 5563 45TH ST. WHILE THE
 COVER SHEET OF THE PLANS HAS 5676
 PREMIER PARK DR?
 2)PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
 NOTE FL S S 713.13(2) IF WORK HAS NOT
 BEEN COMMENCED WITHIN 90 DAYS OF
 RECORDING OF COMMENCEMENT IT WILL BECOME
 NULL AND VOID REQUIRNG A NEW RECORDING
 AT THE CLERK OF THE COURT.
  
 3) 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSLY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORICSURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGNCOMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED
 SITES.ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENET, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCELL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 4) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 5) 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM
 HIGHWINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 6 )W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 7) FBC* 109.3.7SPECIAL INSPECTOR.
 THIS BUILDING WILL REQUIRE A SPECIAL
 INSPECTOR. PLEASE ARRANGE WITH HAROLD
 PISKURA (INSPECTION SERVICES MANAGER)
 TEL:
 561 805 6711, A MEETING INVOLVING THE
 OWNER, SPECIAL JOBSITE INSPECTOR,
 CONTRACTOR.
  
 NOTE: FOR A SPECIAL INSPECTOR PROJECT
 (3) SETS OF ALL PLANS , SUBMITTALS,
 LETTERS, REPORTS AND PRODUCT APPROVALS
 WILL BE REQUIRED FOR REVIEW FOR THE CITY
  
 8) SUBMIT SOILS REPORT:1802.2.1
 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE
 SOIL IS IN DOUBT, OR WHERE A
 LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL REQUIRE THAT THE
 NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH
 1802.6 .
  
 9) THIS WILL BE A REVIEW OF BUILDING# 1
 SINCE SHEET A-1 HAS THIS BUILDING ONLY
 HIGHLIGHTED.PLEASE PROVIDE A SITE PLAN
 INDICATING THE PHASED WORK AREAS PLUS
 THE ACCESSIBLE ROUTE TO THE RIGHT OF WAY
 THAT WILL BE REQUIRED DURING
 CONSTRUCTION OF THE OTHER BUILDINGS.
 A NOTE APPEARS ON THIS SHEET " LOCATION
 OF FUTURE CONC. SIDEWALK FOR SECONARY
 MEANS OF EGRESS. TO BE DONE AT TIME OF
 TENANT IMPROVEMENT.
 1007.1 ACCESSIBLE MEANS OF EGRESS.
 ACCESSIBLE MEANS OF EGRESS SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTIONS
 11-4.1.3 (8), 11-4.1.3 (9) AND 11-4.3.10
 MEANS OF EGRESS. A CONTINUOUS AND
 UNOBSTRUCTED PATH OF VERTICAL AND
 HORIZONTAL EGRESS TRAVEL FROM ANY
 OCCUPIED PORTION OF A BUILDING OR
 STRUCTURE TO A PUBLIC WAY. A MEANS OF
 EGRESS CONSISTS OF THREE SEPARATE AND
 DISTINCT PARTS: THE EXIT ACCESS, THE
 EXIT AND THE EXIT DISCHARGE.
  
  
 10)COVERSHEET BUILDING STATISTICS:
 SINCE THE WRONG CODE IS MENTIONED PLEASE
 PROVIDE THE CORRECTED INFORMATION ON
 BUILDING TYPE,AREA, THE AMOUNT OF FIRE
 PROTECTION TO BE PROVIDED (TYPE AOR B)
 AND IF FIRE SPRINKLERED.
  
 11) COVERSHEET BUILDING STATISTICS:
 INDICATES THIS IS TO BE A FIRE
 SPRINKLERED BUILDING, THE DRAWING INDEX
 DOES NOT APPEAR TO LIST FIRE SPRINKLER
 PLANS, IF TO TAKE CREDITS FOR FIRE
 SPRINKLERS, PLANS WILL BE REQUIRED.
  
 12) COVERSHEET ALSO INDICATES THAT THE
 OCCUPANT LOAD IS FIGURED ON LOW HAZARD
 STORAGE, WILL THE FIRE SPRINKLERS ALSO
 BE BASED ON THIS SAME OCCUPANCY
 CLASSIFICATION? SHEET A-15 LIFE SAFETY
 PLAN ALSO TAKEN ON THE SAME OCCUPANCY.
 2004 FBC302.3 MIXED OCCUPANCIES.
 WHERE A BUILDING IS OCCUPIED BY TWO OR
 MORE USES NOT INCLUDED IN THE SAME
 OCCUPANCY CLASSIFICATION, THE BUILDING
 OR PORTION THEREOF SHALL COMPLY WITH
 SECTION 302.3.1 OR 302.3.2 OR A
 COMBINATION OF THESE SECTIONS.THE
 SUBMITTED LIFE SAFETY PLAN MAY NOT WORK
 IF THE MIXED USE OCCUPANCY IS TAKEN AS
 SHOWN ON A-1 ( OFFICE /SHOWROOM/
 INDUSTRIAL TYPE/ WAREHOUSE RETAIL
 UNITS).
  
 13) SHEET A-2 INDICATES SITE AMENITIES
 WHICH WOULD BE REVIEWED UNDER A SITE
 AMENITIES PACKAGE AND SEPERATE PERMIT.
 11-4.3.2 LOCATION.
 (1)AT LEAST ONE ACCESSIBLE ROUTE
 WITHIN THE BOUNDARY OF THE SITE SHALL BE
 PROVIDED FROM PUBLIC TRANSPORTATION
 STOPS, ACCESSIBLE PARKING, AND
 ACCESSIBLE PASSENGER LOADING ZONES, AND
 PUBLIC STREETS OR SIDEWALKS TO THE
 ACCESSIBLE BUILDING ENTRANCE THEY SERVE.
 THE ACCESSIBLE ROUTE SHALL, TO THE
 MAXIMUM EXTENT FEASIBLE, COINCIDE WITH
 THE ROUTE FOR THE GENERAL PUBLIC.
 (2)AT LEAST ONE ACCESSIBLE ROUTE
 SHALL CONNECT ACCESSIBLE BUILDINGS,
 FACILITIES, ELEMENTS, AND SPACES THAT
 ARE ON THE SAME SITE.
 (3)AT LEAST ONE ACCESSIBLE ROUTE
 SHALL CONNECT ACCESSIBLE BUILDING OR
 FACILITY ENTRANCES WITH ALL ACCESSIBLE
 SPACES AND ELEMENTS AND WITH ALL
 ACCESSIBLE DWELLING UNITS WITHIN THE
 BUILDING OR FACILITY.
 (4)AN ACCESSIBLE ROUTE SHALL
 CONNECT AT LEAST ONE ACCESSIBLE ENTRANCE
 OF EACH ACCESSIBLE DWELLING UNIT WITH
 THOSE EXTERIOR AND INTERIOR SPACES AND
 FACILITIES THAT SERVE THE ACCESSIBLE
 DWELLING UNIT.
 11-4.3.4 PASSING SPACE.
 IF AN ACCESSIBLE ROUTE HAS LESS THAN 60
 INCHES (1525 MM) CLEAR WIDTH, THEN
 PASSING SPACES AT LEAST 60 INCHES BY 60
 INCHES (1525 MM BY 1525 MM) SHALL BE
 LOCATED AT REASONABLE INTERVALS NOT TO
 EXCEED 200 FEET (61 M). A T-INTERSECTION
 OF TWO CORRIDORS OR WALKS IS AN
 ACCEPTABLE PASSING PLACE.
  
 14) 13-101.1.6 SHELL BUILDINGS .
 NONRESIDENTIAL BUILDINGS THAT ARE
 PERMITTED PRIOR TO DESIGN COMPLETION OR
 WHICH WILL BE FINISHED IN SECTIONS AT A
 TIME AFTER CONSTRUCTION OF THE SHELL
 SHALL COMPLY WITH EITHER METHOD B OR C
 OF SUBCHAPTER 13-4 OF THE CODE PRIOR TO
 GRANTING OF A PERMIT TO BUILD. ALL
 ASSUMPTIONS MADE ABOUT FEATURES NOT
 INSTALLED UNTIL LATER THAT ARE NOT ON
 THE BUILDING PLANS SHALL BE LISTED AND
 APPENDED TO THE COMPLIANCE FORM
 SUBMITTED TO THE BUILDING DEPARTMENT.
 UNLESS THE BUILDING IS COMPLETED AS PER
 ALL ASSUMPTIONS MADE IN THE ORIGINAL
 CODE COMPLIANCE SUBMITTAL, A REVISED
 CODE SUBMITTAL(S) USING METHODS A, B OR
 C SHALL BE SUBMITTED WHEN COMPLETION OF
 THE BUILDING (OR PART OF THE BUILDING)
 IS PERMITTED.
 SHELL BUILDINGS
 13-401.2.B.3 SHELL BUILDINGS .
 ONLY THOSE SHADING DEVICES THAT ARE
 INSTALLED AT THE TIME OF CONSTRUCTION OF
 THE BUILDING SHELL SHALL BE CONSIDERED
 WHEN DETERMINING COMPLIANCE FOR SHELL
 BUILDINGS .
  
 15) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 16) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXTERIOR GLAZED SWING DOORS
 B) EXTERIOR SOLID SWING DOORS
 C) ROLL UP OR OVERHEAD DOORS
 D) FIXED WINOWS
 E) OPERATABLE WINDOWS
 F) SKYLIGHTS
 G) MULLIONS VERTICAL/ HORIZONTAL
 H) LOUVERS
 I) STORM SHUTTERS
 J) ROOFING ASSEMBLIES: INSULATION,
 BUILT UP ROOF SYSTEM
 K) PREFABRICATED ROOF A/C STANDS
 *****REVIEW COMMENT# 6 (PRODUCT
 APPROVALS) BY DEIGN PROFESSIONAL********
  
 16A)PROVIDE STORM PANEL INFORMATION
 WITH INSTALLATION SCHEDULE AND KEY PLAN
 WITH SPECIFIC ANCHORS AND MOUNTING TO BE
 USED FOR ALL NON-IMPACT GLAZING.
 FBC 16091.4.
  
 16B)FL BLD CODE 2001 SECTION
 1609.1.4, 1714.5.2. PROCEDURES: 1(B)
 A COMPLETE INSTALLATION SCHEDULE
 SUMMARIZING & IDENTIFYING OPENING SIZES,
 STORY HEIGHTS, UNIT MARK NUMBERS, UNIT
 SPANS/WIDTHS, UNIT STORM BAR REINFORCING
 REQUIREMENTS, WALL PRES- SURE ZONES,
 SLAT TYPES, ETC., SHALL BE SUBMITTED AT
 TIME OF PERMIT APPLICATION TO FACILITATE
 PLAN REVIEW AND PERMIT ISSUANCE.SEE
 THE BUILDING OFFICIALS INTERPRETATION ON
 LARGE OR HIGH RISE BUILDINGS AS FAR AS
 SHUTTERS VS LARGE OR SMALL MISSLE RATED
 GLASS.
 *************************
 QUESTION# 13) RECOGNIZING SUCH CONCERNS
 AS ABSENTEE OWNERS, OR CASES WHERE
 LONGER TIME AND EFFORT IS NECESSARY TO
 SECURE SHUTTERS ON LARGE OR MULTI-STORY
 BUILDINGS, WHAT MEASURES ARE BEING
 RECOMMENDED OR IMPLEMENTED TO ENSURE
 THAT COMPLETE INSTALLATION OR SECURING
 IS DONE SUFFICIENTLY IN ADVANCE OF THE
 HURRICANE EVENT?
  
 IN MATTERS FLORIDA BUILDING CODE, 2004
 EDITION, PROVIDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT
 REQUIREMENTS FOR ENSURING STABILITY,
 STRENGTH, AND PROPER OPERATION OF
 EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF
 SHUTTERS ON LARGE OR MULTI-STORY
 BUILDING, OR MULTIPLE BUILDINGS ON THE
 SAME PROPERTY, PRE-STORM PREPARATION
 PLANS MUST BE SUBMITTED BY THE PROPERTY
 OWNERS OR MANAGING AGENTS FOR REVIEW BY
 THE CONSTRUCTION SERVICES DEPARTMENT.
 ANY SUCH PLAN SHALL INCLUDE, AT A
 MINIMUM, ON-SITE LOCATION OF SHUTTERS,
 PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS (SAID PARTIES MUST BE LOCATED
 WITHIN PALM BEACH COUNTY), TOTAL NUMBER
 OF OPENINGS TO BE PROTECTED AND TOTAL
 TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE
 ACCOMPLISHED WITHIN TWELVE (12) HOURS OR
 LESS OF THE OFFICIAL NOTIFICATION BY THE
 NATIONAL WEATHER SERVICE OF A HURRICANE
 WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND
 THIS STANDARD) ARE NOT INTENDED TO
 PROHIBIT THE USE OF ALTERNATIVE
 MATERIALS AND METHODS, AND ALLOW THE
 BUILDING OFFICIAL TO REVIEW AND APPROVE
 ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE
 RESISTANCE, DURABILITY AND SAFETY
 PRESCRIBED BY CODE. BASED UPON THIS CODE
 PROVISION, ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON
 A CASE-BY-CASE BASIS AND SHALL REQUIRE
 SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING
 THE ALTERNATE.
  
 QUESTION# 14) ARE REMOVABLE STORM PANELS
 APPROPRIATE FOR USE ON VERY LARGE, MID
 OR HIGH-RISE STRUCTURES?
  
 NO, EXCEPT ON THE GROUND FLOOR. ON
 COMMERCIAL AND MULTI-UNIT RESIDENTIAL
 STRUCTURES, ABOVE THE FIRST LEVEL,
 IMPACT RESISTANT GLAZING OR PERMANENTLY
 AFFIXED PROTECTIVE DEVICES SHALL BE
 INSTALLED. PERMANENTLY AFFIXED
 PROTECTIVE DEVICES SHALL REQUIRE THE
 WRITTEN APPROVAL OF THE BUILDING
 OFFICIAL.
 16C) NOTE: A-3 INDICATE THE STORAGE
 OF STORM SHUTTERS APPEARS TO BE WITHIN
 THE TENANT BUILD OUT AND NOT IN A COMMON
 A STORAGE AREA DESIGNATED FOR STORM
 SHUTTERS.
  
 17) A-3 PLANS APPEAR TO BE CODE
 COMPLIANT FOR EGRESS AS A SHELL BUILDING
 BUT WHEN THE BREAK UP INTO TENANT BUILD
 OUTS EACH SPACE MAY NOT APPLY.
 BEWARE OF VERTICAL ACCESSIBILITY
 REQUIREMENTS FOR EGRESS.
 11-4.1.3(8)IN NEW CONSTRUCTION, AT
 A MINIMUM, THE REQUIREMENTS IN SECTION
 11-4.1.3 (8)(A) AND SECTION 11-4.1.3
 (8)(B) BELOW SHALL BE SATISFIED
 INDEPENDENTLY:
 (A)(I)AT LEAST 50 PERCENT OF ALL
 PUBLIC ENTRANCES [EXCLUDING THOSE IN
 SECTION 11-4.1.3 (8)(B) BELOW] MUST BE
 ACCESSIBLE. AT LEAST ONE MUST BE A
 GROUND-FLOOR ENTRANCE. PUBLIC ENTRANCES
 ARE ANY ENTRANCES THAT ARE NOT LOADING
 OR SERVICE ENTRANCES.
 (II)ACCESSIBLE ENTRANCES MUST BE
 PROVIDED IN A NUMBER AT LEAST EQUIVALENT
 TO THE NUMBER OF EXITS REQUIRED BY THE
 APPLICABLE BUILDING/FIRE CODES. (THIS
 PARAGRAPH DOES NOT REQUIRE AN INCREASE
 IN THE TOTAL NUMBER OF ENTRANCES PLANNED
 FOR A FACILITY.)
  
 18) A-5
 18A) INDICATES POSITIVE AND NEGATIVE
 PRESSURES FOR OPENINGS BUT NO CRITERIA
 AS TO WIND DESIGN?1603.1.4 WIND DESIGN
 DATA.
 THE FOLLOWING INFORMATION RELATED TO
 WIND LOADS SHALL BE SHOWN, REGARDLESS OF
 WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL-FORCE-RESISTING SYSTEM OF
 THE BUILDING:
 1.BASIC WIND SPEED (3-SECOND GUST),
 MILES PER HOUR (KM/HR).
 2.WIND IMPORTANCE FACTOR, I W , AND
 BUILDING CLASSIFICATION FROM TABLE
 1604.5 OR TABLE 6-1, ASCE 7 AND BUILDING
 CLASSIFICATION IN TABLE 1-1, ASCE 7.
 3.WIND EXPOSURE, IF MORE THAN ONE
 WIND EXPOSURE IS UTILIZED, THE WIND
 EXPOSURE AND APPLICABLE WIND DIRECTION
 SHALL BE INDICATED.
 4.THE APPLICABLE ENCLOSURE
 CLASSIFICATIONS AND, IF DESIGNING WITH
 ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5.COMPONENTS AND CLADDING. THE
 DESIGN WIND PRESSURES IN TERMS OF PSF
 (KN/M 2 ) TO BE USED FOR THE DESIGN OF
 EXTERIOR COMPONENT AND CLADDING
 MATERIALS NOT SPECIFICALLY DESIGNED BY
 THE REGISTERED DESIGN PROFESSIONAL.
 ONCE THIS INFORMATION IS KNOWN THE
 PRESSURE ZONES AND BE REVIEWED.
  
 18B) THE ELEVATIONS DO NOT INDICATE
 WHICH OPENINGS ARE IN THE END ZONE AND
 INTERIOR ZONES, PLEASE INDICATE ZONES
 ON THE ELEVATION.
  
 19) A-6 SIDEWALK NOTE MAX SLOPE 1:12 ,
 MAX RISE AND MAX RUN OF 6'-0" IS
 THEACTUALL DEFINITION OF A RAMP WITHOUT
 REQUIRED GUARDRAILS. NO MENTION OF MAX
 CROSS SLOPE OF WALKWAY.
  
 20)SHEET A-7:
 20A) SLAB INFORMATION IS MISSING VAPOR
 BARRIER. 1911.1 THE THICKNESS OF
 CONCRETE FLOOR SLABS SUPPORTED DIRECTLY
 ON THE GROUND SHALL NOT BE LESS THAN 3 1
 / 2 INCHES (89 MM). A 6-MIL [0.006 INCH
 (152 MM)] POLYETHYLENE VAPOR RETARDER
 WITH JOINTS LAPPED NOT LESS THAN 6
 INCHES (152 MM) SHALL BE PLACED BETWEEN
 THE BASE COURSE OR SUBGRADE AND THE
 CONCRETE FLOOR SLAB, OR OTHER APPROVED
 EQUIVALENT METHODS OR MATERIALS SHALL BE
 USED TO RETARD VAPOR TRANSMISSION
 THROUGH THE FLOOR SLAB.
  
 20B) DETAIL 4 PROVIDE ADDITIONAL
 INFORMATION ON THE TYPE OF TRIM AT THE
 TOP OF THE BUILDING.
  
 20C) DETAIL# 1 AT THE SEAT OF THE BAR
 JOIST THE WALL IS CUT TO A DEPTH OF
 2/3RDS THE THICKNESS NO REBAR INDICATED,
 PLEASE EXPLAIN RATIONAL?A14 DETAIL 1 & 2
 SAME DETAIL?
  
 21) S5.2 THE DESIGN CRITERIA NEEDS TO BE
 UPDATED TO THE 2004 FBC.
  
 22) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.