| Notes |
| Date |
Text |
| 2005-10-07 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1- NEED RECORDED NOTICE OF COMMENCEMENT. | | | | | | 2- THERE IS NOT INFORMATION PROVIDED TO | | | DETERMINE HOW IS THE SLAB GOING TO BE | | | REINFORCED FOR FUTURE SCREEN ENCLOSURE. | | | PROVIDE DETAILS AND SPECIFICATIONS FOR | | | STRUCTURAL CONCRETE SLAB FOOTING | | | REINFORCEMENT AT THE EDGES. SECTION | | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | | SPECIFY: | | | A)CONCRETE SLAB THICKNESS AND | | | REINFORCEMENT. IS IT GOING TO HAVE | | | WIREMESH OR IS IT GOING TO BE FIBERMESH | | | CONCRETE THAT DOESN'T REQUIRE WIREMESH | | | REINFORCEMENT? | | | B)FOOTING SIZE: WIDTH AND DEPTH. | | | C)FOOTING STEEL REINFORCEMENT SIZE AND | | | NUMBER OF BARS. | | | | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712. |
|