Plan Review Notes
Plan Review Notes For Permit 05090589
Permit Number 05090589
Review Stop B
Sequence Number 1
Notes
Date Text
2005-10-07 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- THERE IS NOT INFORMATION PROVIDED TO
 DETERMINE HOW IS THE SLAB GOING TO BE
 REINFORCED FOR FUTURE SCREEN ENCLOSURE.
 PROVIDE DETAILS AND SPECIFICATIONS FOR
 STRUCTURAL CONCRETE SLAB FOOTING
 REINFORCEMENT AT THE EDGES. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 SPECIFY:
 A)CONCRETE SLAB THICKNESS AND
 REINFORCEMENT. IS IT GOING TO HAVE
 WIREMESH OR IS IT GOING TO BE FIBERMESH
 CONCRETE THAT DOESN'T REQUIRE WIREMESH
 REINFORCEMENT?
 B)FOOTING SIZE: WIDTH AND DEPTH.
 C)FOOTING STEEL REINFORCEMENT SIZE AND
 NUMBER OF BARS.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.