| 2006-04-09 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6652 |
| | E-MAIL: [email protected] |
| | |
| | REVISION TO REDUCE HEIGHT OF ENTRY |
| | DOORS, AND SUBMITTAL FOR ALTERNATIVE |
| | STORM PANEL SHUTTERS TO ADDRESS PROVISO. |
| | |
| | 1) ONLY ONE COPY OF REVISED SHEETS A-3.0 |
| | AND A-4.1 WAS SUBMITTED.TWO SIGNED AND |
| | SEALED COPIES OF EACH REVISED SHEET |
| | SHOULD HAVE BEEN SUBMITTED, ONE COPY FOR |
| | PERMIT FILE AND ONE FOR THE JOB SITE. |
| | |
| | 2) THE SUBMITTED SHEETS A-3.0 AND A-4.1 |
| | ARE REVISIONS OF THE SHEETS REVIEWED FOR |
| | PERMIT ISSUANCE.THEY WERE BROUGHT IN |
| | AS SUBMITTALS, WHEN THEY ARE IN FACT |
| | REVISIONS.A REVISION FEE OF $70 IS |
| | DUE.THE FEE IS DERIVED FROM THE |
| | STANDARD REVISION FEE OF $50 PLUS $10 |
| | PER REVISED SHEET (IN THIS CASE, TWO |
| | SHEETS).PLEASE PAY THE REQUIRED FEE |
| | WHEN RESUBMITTING. |
| | |
| | 3) AS NOTED IN COMMENTS 1 AND 2, ABOVE, |
| | THE PLANS HAVE BEEN REVISED TO REDUCE |
| | THE STOREFRONT DOOR HEIGHT TO MATCH THE |
| | SCOPE OF THE STOREFRONT DOOR PRODUCT |
| | APPROVALS THAT WERE PREVIOUSLY |
| | SUBMITTED.PRIOR TO THE PLAN REVISION, |
| | THE STOREFRONT DOOR PRODUCT APPROVALS |
| | COULD NOT BE STAMPED AS SUITABLE FOR THE |
| | PROJECT, SO ALL COPIES WERE RETURNED TO |
| | YOU, UNSTAMPED.NOW THAT THE PLANS HAVE |
| | BEEN REVISED, TWO COPIES OF THE |
| | STOREFRONT DOOR PRODUCT APPROVALS MUST |
| | BE SUBMITTED FOR REVIEW.THE PRODUCT |
| | APPROVALS THAT WERE PREVIOUSLY SUBMITTED |
| | ARE ARCH ALUMINUM STOREFRONT DOOR |
| | PRODUCT APPROVALSNOA# 01-0226.05 AND |
| | 02-0904.02. |
| | |
| | 4) ONLY ONE COPY OF THE POMA CORPORATION |
| | ALUMINUM STORM PANEL SHUTTER PRODUCT |
| | APPROVAL NOA# 02-0417.06 WAS SUBMITTED. |
| | TWO COPIES ARE REQUIRED.ALSO, THE |
| | STATEWIDE PRODUCT APPROVAL COVER SHEET |
| | WAS NOT SUBMITTED.I HAVE PRINTED THE |
| | RELEVANT COVER SHEET AND ATTACHED IT TO |
| | THE SUBMITTED PRODUCT APPROVAL SO THAT |
| | TWO COMPLETE COPIES CAN BE RESUBMITTED, |
| | ASSUMING COMMENT 5, BELOW, CAN BE |
| | ADDRESSED WITHOUT HAVING TO SELECT A |
| | DIFFERENT SHUTTER SUPPLIER. |
| | |
| | 5) ARCHITECTURAL PLAN SHEET A-4.1 AND |
| | MODULAR BUILDING PLAN SHEET 7 OF 7, SHOW |
| | DOOR AND WINDOW BUCKS OF 1"X 4" P.T. |
| | WOOD, SCREWED TO THE METAL FRAME |
| | STRUCTURE.SHEET A-4.1 SHOULD BE |
| | REVISED TO SHOW HOW THE SHUTTERS WILL BE |
| | ANCHORED, IN ACCORDANCE WITH THE PRODUCT |
| | APPROVAL, TO THE STEEL FRAME STRUCTURE. |
| | ALSO, THE SAME COMMENT ALSO APPLIES TO |
| | ANCHORING OF THE STOREFRONT PER THE |
| | SUBMITTED ARCH ALUMINUM PRODUCT |
| | APPROVAL.PROVIDE THE REQUIRED |
| | ADDITIONAL DETAILS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |