| 2006-02-23 00:00:00 | BUILDING PLAN REVIEW |
| | ******PROVISO******* |
| | ROBERT BROWN(561) 805 6652 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | F.S.= FLORIDA (STATE) STATUTE |
| | |
| | --PROVISO-- |
| | FBC 1606.1SUBMIT ALTERNATIVE |
| | STOREFRONT DOOR PRODUCT APPROVALS OR |
| | REVISE THE PLANS.THE SUBMITTED ARCH |
| | ALUMINUM STOREFRONT DOOR PRODUCT |
| | APPROVALS REFERENCE MIAMI-DADE NOA# |
| | 01-0226.05 AND 02-0904.02.BOTH |
| | DOCUMENTS SHOW A MAXIMUM DOOR FRAME |
| | HEIGHT OF 97" WHICH IS LESS THAN THE |
| | PROPOSED 120" (9'-2") DOOR FRAME SHOWN |
| | ON SHEET A-4.1 OF THE PLANS.THE 120" |
| | DOOR IS OUTSIDE OF THE SCOPE OF THE |
| | SUBMITTED PRODUCT APPROVALS. |
| | |
| | --PROVISO-- |
| | FBC 1606.1.4SUBMIT AN ALTERNATIVE |
| | STORM PANEL SHUTTER PRODUCT APPROVAL. |
| | THE SUBMITTED EASTERN METAL SUPPLY |
| | SHUTTER PRODUCT APPROVAL REFERENCES |
| | MIAMI-DADE NOA# 03-0716.02 WHICH STATES |
| | THAT THE MAXIMUM ALLOWABLE STORM PANEL |
| | LENGTH IS 9'-0".THE PLANS SHOW |
| | STOREFRONT WINDOWS THAT EXCEED 9'-0", |
| | BOTH HORIZONTALLY AND VERTICALLY.THESE |
| | WINDOW SIZES ARE OUTSIDE THE SCOPE OF |
| | THE SUBMITTED PRODUCT APPROVAL |
| | |
| | |