| Date |
Text |
| 2005-11-12 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 BUILDING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHT A-1.0 SUBMIT A DETAIL FOR THE |
| | FOUNTAIN. INDICATE IF WATER SERVICE WILL |
| | BE CONNECTED TO THE FOUNTAIN. IF SO, |
| | BACKFLOW PROTECTION WILL BE REQUIRED. |
| | SECTIONS 104.2.1. & 608. - INDICATE IF |
| | FOUNTAIN WILL HAVE A DRAIN TO SANITARY. |
| | IF SO A BACKWATER VALVE MAY BE RQUIRED. |
| | 2. SHT S2 NOTE "PROVIDE SCUPPERS & |
| | DOUBLE DRAINAGE SYSTEM". PLEASE INDICATE |
| | IF PARAPET WALLS WILL BE BUILT AROUND |
| | TRAILERS. SUBMIT CALCULATIONS FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS IF |
| | THIS IS THE CASE. SHOW SQUARE FEET OF |
| | ROOF PLUS 1/2 AREA OF ALL VERTICAL WALLS |
| | INCLUDING PARAPETS ADDED TO SF OF ROOF |
| | IN CALCULATIONS. INDICATE LOCATION OF |
| | PRIMARY AND SECONDARY ROOF DRAINS, AS |
| | WELL AS THE SIZE OF EACH. SHOW HEIGHT |
| | AND WIDTH OF ALL SCUPPERS AS WELL AS A |
| | DETAIL SHOWING THE SCUPPERS MEASUREMENT |
| | FROM THE ROOF TO THE FLOW LINE OF EACH |
| | TYPE OF SCUPPER. (PRIMARY OR OVERFLOW). |
| | IF DOWNSPOUTS WILL BE USED INDICATE SIZE |
| | OF DOWNSPOUTS. SECTIONS 1106 & 1107 AND |
| | ALL SUBSECTIONS. ALSO SECTION 1503.4.2. |
| | 3. SHTS LC-1 THRU LC-4 TITLE BLOCK |
| | REQUIRED BY FAC 61G1-16.004 IS REQUIRED |
| | ON EACH SHEET. SHOW ALL REQUIRED |
| | INFORMATION REQUIRED BY FAC AND FS |
| | 481.301. - THE PERSONAL SIGNATURE OF THE |
| | LANDSCAPE ARCHITECT IS REQUIRED ON THE |
| | SEAL. IT APPEARS THAT INITIALS WERE |
| | USED. A SIGNED, SEALED, NOTORIZED LETTER |
| | WITH PROPER TITLE BLOCK SHALL BE |
| | SUBMITTED FOR OUR FILE TO INDICATE LEGAL |
| | SIGNATURE. |
| | 4. SHT LC-3 BACKFLOW FOR IRRIGATION |
| | SHALL BE PERMITTED AND INSTALLED BY A |
| | LICENSED PLUMBING CONTRACTOR. |
| | 5. SHT 2 OF 7 BREAK AREA SINK SHALL BE |
| | ACCESSIBLE. SUBMIT A DETAIL SHOWING |
| | COMPLIANCE WITH SECTION 11-4.24 AND ALL |
| | SUBSECTIONS. SHOW REQUIRED FRONTAL |
| | APPROACH CLEAR FLOOR SPACE. |
| | 6. PER TABLE 403.1 A DRINKING FOUNTAIN |
| | IS REQUIRED. SUBMIT A DETAIL SHOWING |
| | COMPLIANCE WITH SECTION 11-4.15 AND ALL |
| | SUBSECTIONS AS WELL AS SECTION |
| | 11-4.1.3(10)(A) REQUIREMENTS FOR THOSE |
| | WHO HAVE DIFFICULTY BENDING OR STOOPING. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |