| Plan Review Notes For Permit 05090560 |
| Permit Number |
05090560 |
|
| Review Stop |
ENG |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-09-16 00:00:00 | FAILED: | | | | | | 1. SHEET C-5 STRUCTURE NO.1 WITH | | | W.I.D.B., SHEET C-7 SHOWS IT AS CONTROL | | | STRUCTURE #101, PLEASE CORRECT. | | | 2. SHEET C-5 SHOWS INLETS STRUCTURES 1& | | | 2 AS C-4 TYPE, TABLE ON SHEET C-7 SHOWS | | | OTHER TYPE, DIMENSIONS DO NOT MATCHE | | | THE CONTROL STRUCTURE #101, PLEASE | | | VERIFY. | | | 3. SHEET C-7 NO DIMENSIONS FOR THE | | | PROPOSED EXFILTRATION ARE GIVEN. ALSO | | | VERIFY THE I.E=14.5 WITH ESTIMATED | | | SEASONAL HIGH WATER LEVEL=8.00. | | | 4. SHEET C-7 NO DIMENSIONS FOR THE | | | PROPOSED DUMPSTER ENCLOSURE ARE | | | PROVIDED, IF CITY PICK UP, THEN SIZE PER | | | THE CITY REQUIREMENTS. | | | 5. SHEET C-7, APPROACH AS SHOWN DOES NOT | | | MATCH STANDARD GC-4.1 ON SHEET C-8, | | | PLEASE VERIFY. | | | 6. PLEASE SUBMIT CIVIL PLANS TO THE | | | PUBLIC UTILITIES AND ENGINEERING FOR | | | APPROVAL OF ALL THE CONNECTION TO THE | | | CITY SERVICES, 494-1085, MANNY GONZALEZ. | | | | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|