Plan Review Notes
Plan Review Notes For Permit 05090555
Permit Number 05090555
Review Stop E
Sequence Number 1
Notes
Date Text
2005-09-27 00:00:00************ UNSAT **************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANEL SCHEDULES.
 PLEASE SEE RISER SHOWS THREE PANELS
 BEING FED FROM EXISTING MDP, HOWEVER MDP
 ONLY SHOWS FEEDS TO PANEL "A" AND PANEL
 "B"? PLEASE CLARIFY WHERE FED TO PANEL
 "C" IS LOCATED.
 PLEASE IDENTIFY ALL PANELS ON RISER
 DIAGRAM.
 PLEASE SEE RISER SHOWS ONE "NEW" PANEL
 BEING FED FROM MDP , HOWEVER PLANS
 INDICATE ALL PANELS AN "EXISTING " AND
 PANEL SCHEDULES ALSO INDICATE ALL PANEL
 SCHEDULES AS EXISTING.??
 215.5
  
 2)NOTE: PLEASE INDICATE OF NEW OR
 EXISTING ROOF-TOP GFI IS PROVIDED.
 210.63
  
 3)NOTE; PLEASE INDICATE NEW OR EXISTING
 REQUIRED SIGN CIRCUIT PER 600.5
  
 4)NOTE: PLEASE SEE 210.62 FOR REQUIRED
 "SHOW WINDOW" RECEPTS.
 PLEASE SEE OCCUPANCY NOW INDICATES AN
 NEW "SHOWROOM".
 NEW RECEPTS LOCATED ABOVE WINDOWS WILL
 BE REQUIRED.
 PLEASE SEE 220.12 FOR LOAD CALCUALTIONS
 AND CIRCUITING.220.3B7
  
 5)NOTE: PLEASE SEE SOME ITEMS INDICATED
 AS "E" (EXISTING ) ON PLANS AND SOME
 NEW, AND SOME ??
  
 6)NOTE: PLEASE NOTE/ CIRCUIT EM/ EXT LTS
 PER 700.12E.
 PLEASE SEE THAT ALL EM/EXT LTS SHALL BE
 CIRCUITED TO THE LOCAL BRANCH CIRCUIT
 FEEDING AREA.
  
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED PLANS AND
 ONLY INSERT NEW REVISED PLANS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]