| 2005-10-17 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- CONTRACTOR'S LICENSE IS FOR ALUMINUM |
| | SPECIALTIES. WINDOW INSTALLTION IS OUT |
| | OF THE SCOPE OF WORK FOR THIS LICENSE. |
| | NEED CONTRACTOR WITH GLASS AND GLAZING |
| | LICENSE TO APPLY FOR THIS PERMIT. |
| | |
| | 2- BEDROOM WINDOWS NEED TO COMPLY WITH |
| | MIN. SIZE AS REQUIRED BYSEC. 1005.4.4 |
| | FBC 2001. MIN. SIZE IS 24" CLEAR OPENING |
| | HEIGHT, 20" CLEAR OPENING WIDTH AND |
| | 5.7S.F. MIN. CLEAR OPENING. CLEARLY |
| | IDENTIFY ON KEY PLAN BEDROOM WINDOWS AND |
| | REVISE WINDOW SIZE AS REQUIRED TO COMPLY |
| | WITH CITED SEC. ABOVE. |
| | |
| | 3- DADE COUNTY NOA SUBMITTED IS NOT THE |
| | SAME THAT WAS SUBMITTED FOR FLORIDA |
| | PRODUCT APPROVAL. NEED NOA #03-0514.01 |
| | AND MAKE SURE THAT COPIES ARE LEGIBLE. |
| | |
| | 4- PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR: |
| | A) WINDOW MULLIONS. |
| | B) IMPACT WINDOWS WITH FROSTED GLASS AS |
| | SPECIFIED FOR BATHROOMS. |
| | |
| | 5- DESIGN PRESSURES CHART IS NOT |
| | LEGIBLE. NEED A CLEAR ONE. |
| | |
| | 6- NEED RECORDED NOTICE OF COMMENCEMENT. |
| | |
| | 7- THERE ARE 2 BUILDINGS IN THIS |
| | PROPERTY. SPECIFY WHICH BUILDING IS THE |
| | ONE HAVING THE WINDOWS REPLACED. |
| | |