Plan Review Notes
Plan Review Notes For Permit 05090549
Permit Number 05090549
Review Stop E
Sequence Number 1
Notes
Date Text
2005-12-14 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} LOCATE ALL THE GENERATOR AND SERVICE
 EQUIPMENT ON THE SURVEY OR DRAW A SITE
 PLAN, SO THAT COMPLIANCE WITH 225.31
 THROUGH 225-37 CAN BE DETERMINED.
  
 2} THE LOAD CALCULATION SUBMITTED IS 173
 AMPS, THE OUTPUT OF THE GENERATOR IS 154
 AMPS MAX.SUGGEST SETTING A SUBPANEL WITH
 SELECTED LOADS TO MATCH THE OUTPUT. SEE
 702.5.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR
 THE PLAN MUST PRINT AND SIGN THEIR NAME
 TO THE PLAN. 104.2.1 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  
  