| Notes |
| Date |
Text |
| 2005-10-12 00:00:00 | 1) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) THE CITY OF WPB DOES NOT USE THE | | | SOUTH FLORIDA BUILDING CODE BOOK. THE | | | CODE BOOK WE USE IS THE FLORIDA BUILDING | | | CODE 2001. HOWEVER, AS OF OCTOBER 1ST WE | | | WILL BE USING THE 2004 FLORIDA BUILDING | | | CODE BOOK. | | | | | | 3) IF THIS STRUCTURE IS DESIGN UNDER THE | | | 2001 CODE, IT WILL HAVE TO BE DESIGNED | | | TO WITH-STAND 140MPH WITH THE CANVAS | | | AWNING IN PLACE.SEE FBC 2001 SEC. | | | 1606.1.6 AND 1606.1.7 FOR BASIC WIND | | | SPEEDS. | | | | | | 4) IF THIS STRUCTURE IS DESIGNED FOR THE | | | CANVAS TO BE REMOVED AT 75MPH WIND | | | SPEED. IT WILL HAVE TO BE DESIGN USING | | | THE 2004 CODE.SEC 3105. ALSO A NOTORIZE | | | LETTER FROM THE OWNER STATING THAT THE | | | CANVAS WILL BE REMOVED AT WIND SPEEDS OF | | | 75MPH SHALL BE SUBMITTED FOR REVIEW. | | | | | | 5) WHAT IS THE HEIGHT OF THE STRUCTURE? | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] |
|