Plan Review Notes
Plan Review Notes For Permit 05090521
Permit Number 05090521
Review Stop M
Sequence Number 2
Notes
Date Text
2005-11-22 00:00:00*** DENIED ***
 1) DUCT FROM AHU TO TRIANGLE IS NOT
 SIZED.
 2) LOCATION OF CONDENSER UNIT AND DRAIN
 LINE NOT SHOWING ON MECH. PLANS.
 3) SALES PRODUCT BOOKLET DOES NOT
 ADDRESS INSTALLATION DETAILS AND
 REQUIRMENTS FOR AN APPROVED HOOD OVER
 GRILL IN SUMMER KITCHEN. PLEASE SUPPLY A
 DETAILED MANUFACTURE'S SPECIFICATION'S
 AND INSTALLATION INSTRUCTIONS, OR AN
 APPROVED HOOD OVER GRILL.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.