| Date |
Text |
| 2005-10-09 00:00:00 | IN ELEC FOR REVIEW. |
| | ****** UNSAT ****** |
| | |
| | 1)NOTE: PLEASE SUBMIT ALL MANUFACTURES |
| | SPECS/CUT SHEETS FOR NEW GENERATORS, |
| | FIRE PUMP CONTROLLER, NEW ATS |
| | SWITCHE(S), GEN SYSTEM CONTROL MODULE |
| | (PARALLEL OPERATION MODULE). |
| | PLEASE KNOW, CODE COMPLIANCE FOR SOME |
| | ITEMS CAN NOT VERIFIED AT THIS TIME. |
| | PLEASE SEE OTHER COMMENTS. |
| | |
| | 2)NOTE: PLEASE SEE CODE REFERENCES ALL |
| | NEED TO BE UPDATED. |
| | NFPA-70, 2002 WHICH WAS ADOPTED ON JULY |
| | 1ST, 2003. |
| | NFPA-101 2003, NFPA-20 2003, ETC. |
| | PLEASE SEE THAT ALL NFPA'S AS LISTED ON |
| | X-1 COVER SHEET SHOULD BE UPDATED TO THE |
| | LATEST ADOPTED CODES. |
| | DATE OF 3/2/04 ABOVE LISTING IS NOT |
| | ACCURATE TO UPDATE AS SOME OF THESE |
| | CHANGED BEFORE THIS DATE AND SOME HAVE |
| | CHANGED SINCE. |
| | |
| | 3)NOTE: PLEASE SEE NOTE #8 ON E-1 |
| | MENTIONS A "TEMPORARY ELECTRICAL |
| | SERVICE" FOR ANY DOWN TIMES, THIS IS |
| | FINE HOWEVER, NO ELECTRICAL PLANS WERE |
| | SUBMITTED FOR THIS? |
| | PLEASE KNOW, IT MAY BE EASIER TO PERMIT |
| | THIS TEMP SERVICE UNDER A SEPARATE |
| | PERMIT? |
| | |
| | 4)NOTE: PLEASE PLACE ALL ROOM AND AREA |
| | DESIGNATIONS ON NEW BASEMENT LEVEL |
| | PLANS. |
| | |
| | 5)NOTE: PLEASE SEE EGRESS DOORS AND |
| | REQUIREMENTS FROM MAIN ELECTRICAL |
| | ROOM/EMERGENCY ELECTRICAL ROOM. |
| | PLEASE SEE 110.26, FOR DOOR SWING, PANIC |
| | HARDWARE ETC REQUIRED. PLEASE SEE THERE |
| | MAY BE A CONFLICT WITH DOOR SWING FROM |
| | BOILER ROOM? |
| | |
| | 6)NOTE: PLEASE SEE SECTION/DETAIL 2 ON |
| | E-5, WHICH APPEARS TO SHOW SOME SORT OF |
| | ?? DIRECTLY IN FRONT OF DOORS FOR EM |
| | SWGR RM.?? |
| | 110.26 |
| | |
| | 7)NOTE: PLEASE SEE FIRE REVIEW COMMENTS |
| | PERTAINING TO "FIRE WATCH" AS LISTED IN |
| | NOTE ON E-6, WHICH MENTIONS FIRE WATCH |
| | ETC. |
| | PLEASE SEE FIRE REVIEW COMMENTS AS ALL |
| | APPROVALS FOR SUCH MUST BE BY THE FIRE |
| | MARSHALS OFFICE AND AHJ. |
| | PLEASE KNOW, THE AGENCY TO PERFORM SUCH |
| | A WATCHMUST FIRST BE APPROVED BY ABOVE |
| | MENTIONED AND MUST SUBMIT ALL |
| | INFORMATION WHICH WILL BE REQUIRED AND |
| | SET-FORTH BY THE FIRE MARSHALS OFFICE. |
| | |
| | 8)NOTE: PLEASE PROVIDE BATTERY BACK UP |
| | FIXTURES IN MAIN ELECTRICAL ROOM, |
| | GENERATOR ROOM, FIRE PUMP ROOM, CHILLER |
| | ROOM FOR EGRESS TO AND FROM ALL |
| | ELECTRICAL EQUIPMENT WHICH MAY NEED TO |
| | BE TURNED OFF ETC. |
| | LS 101,7.8,7.9, 700.16, |
| | |
| | 9)NOTE: PLEASE SEE THAT GEN ANNUNCIATOR |
| | PANEL/STATUS CONTROL PANEL SHALL BE |
| | LOCATED AT CENTRAL STATION CONTROL |
| | RM/AREA. |
| | 110, 5.6.5, 101,11.8.5 ETC. |
| | |
| | 10)NOTE: PLEASE PROVIDE NOTE FOR 517.17C |
| | FOR TESTING GFP. |
| | |
| | 11)NOTE: PLEASE SEE GSB1 AND GSB2, WHICH |
| | INDICATES 1800A MCB'S?. PLEASE VERIFY |
| | THIS AS 1800 IS NOT A RECOGNIZED SIZE OF |
| | OCP AS SET FORTH UNDER 240.6. |
| | |
| | 12)NOTE: PLEASE PROVIDE LOAD FORGSB? |
| | LOADS FOR OTHER MAINS ETC SHOWN, HOWEVER |
| | THIS COULD NOT BE LOCATED. |
| | 215.5,220 |
| | |
| | 13)NOTE: PLEASE CLARIFY OF ANY MEANS OF |
| | OCP IS LOCATED AT GENERATOS. |
| | 215.5 SEE PREVIOUS NOTE WHICH REQUESTED |
| | MORE INFORMATION FOR GEN SYSTEM MODULE |
| | AND PARALLEL OPERATION. |
| | |
| | 14)NOTE: PLEASE KNOW, THE |
| | OCP/DISCONNECTING MEANS FOR FIRE PUMP |
| | LOCATED IN GSB, WILL BE REQUIRED TO BE |
| | LOCATED OUT OF THIS EQUIPMENT. THIS OCP |
| | AND DISCONNECTING MEANS SHALL BE LOCATED |
| | AHEAD OF GSB. PLEASE SEE NFPA -20 |
| | 9.3.2.2.3.2.695.4B2 |
| | SECTIONS OF 695 AND CHAPTER 9, (9.6) |
| | DOES NOT SPECIFY THE DISCONNECTING MEANS |
| | LOCATION. THE ONLY STATEMENT AS |
| | MENTIONED IN NFPA-20 9.6.1.2 IS"A TAP |
| | AHEAD OF THE ON-SITE GENERATOR |
| | DISCONNECTING MEANS SHALL NOT BE |
| | REQUIRED". |
| | IT IS THE INTERPETATIONTHAT CONNECTION |
| | AS SHOWN MAY VERY WELL PROMOTE AN |
| | INADVERANT DISCONNECT OF FIRE PUMP. |
| | |
| | 15)NOTE: PLEASE KNOW, AS CONVERSED WITH |
| | ELECTRICAL ENGINEER AND ELECTRICAL |
| | CONTRACTOR AND AS DETERMINED UNDER |
| | NFPA-20,9.1.3,9.3.1 NFPA-70 695.4, 695.6 |
| | THE ROUTING OF THE SERVICE ENTRANCE |
| | CONDUCTORS AND FEEDERS SOURCES SHALL BE |
| | PROTECTED BY BEING CONSIDERED "OUTSIDE" |
| | THE BLDG. THE FIRE RATING ALONE FOR |
| | PROTECTION OF CONDUCTORS IS ONLY ONE |
| | CONSIDERATION WHICH IS GIVEN BY ABOVE |
| | MENTIONED 9.3.1. |
| | PLEASE PROVIDE A LAYOUT FOR NEW PROPOSED |
| | ROUTING AND DETAIL PROTECTION. |
| | IT IS KNOWN TO THIS OFFICE AND FIRE |
| | MARSHALS OFFICE; ANEW FEED FROM FPL IS |
| | BEING CONSIDERED WHICH IS PROPOSED TO |
| | EXSITING FIRE PUMP ROOM. |
| | THIS SEEMS TO BE SAFEST AND MOST COST |
| | EFFECTIVE OPTION TO MEET CODE AND LIFE |
| | SAFETY OF NEW INSTALLATION. THISIS |
| | REQUIRED AND ACCEPTABLE DUE TO THE SCOPE |
| | OF WORK AND PERMITTED UNDER NFPA-20 AND |
| | NFPA-70.IN FACT THIS IS THE |
| | RECOMMENDED INSTALLATION. |
| | |
| | 16)NOTE: PLEASE SHOW/DETAIL ON HOW NEW |
| | SERVICE ENTRANCE CONDUCTORS FOR SERVICE |
| | ARE BEING ROUTED. |
| | EXISTING CONDITIONS SHOW MAINS/EMERGENCY |
| | AND |
| | NORMAL LOCATED IN BASEMENT AND NEW |
| | INSTALLATION IS BEING SHOWN ON THE FLOOR |
| | ABOVE (GROUND FLR), YET IT IS UNCLEAR |
| | HOW THE CONDUCTORS ARE GOING TO ENTER |
| | NEW EQUIPMENT. |
| | PLEASE SEE 240.6, 230.70 ETC FOR |
| | CONDUCTORS TO BE CONSIDERED OUTSIDE THE |
| | BUILDING. |
| | |
| | 17)NOTE: PLEASE BE SURE NEW FIRE PUMP |
| | CONTROLLER CONTAINS THE MANUAL MEANS OF |
| | DISCONNECT LOCATED ON THE OUTSIDE OF THE |
| | NEW FPC, THIS DISCONNECTING MEANS SHALL |
| | BE RATED FOR THE FULL LOAD TO BE SERVED. |
| | 230.76,230.79, NFPA-20 10.4.2 |
| | |
| | *************************************** |
| | PLEASE KNOW, I AM RECOMMENDING AN |
| | "ON-SITE" MEETING BE HELD TO GO OVER |
| | PROPOSED WORK. THIS MEETING SHOULD BE |
| | ATTENDED BY THEELECTRICAL ENGINEER OF |
| | RECORD, ELECTRICAL CONTRACTOR, CHIEF |
| | FIRE MARSHAL, CHIEF ELECTRICAL INSPECTOR |
| | AND MYSELF. |
| | THIS WILL HELP IN THE PROCESS FOR THE |
| | SCOPE OF WORK PROPOSED. |
| | PLEASE CONTACT FOR TIME. |
| | |
| | ** PLEASE SEE POSSIBLE REVIEW NOTES FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | AND ONLY INSERT NEW REVISED SHEETS INTO |
| | TWO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | PLEASE SUBMIT "ONE" SET OF THE |
| | OLD/VOIDED SHEETS FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6717 |
| | [email protected] |