| 2005-10-18 00:00:00 | DENIED: | | | 1.PLAN SHEET M-1, OUTSIDE AIR SCHEDULE | | | INDICATES 2 AHU-2 ON AHU-3 IS NOT LISTED | | | PLEASE CLARIFY & CORRECT. | | | | | | 2.PLAN SHEET P-1 INDICATES THE | | | AUXILIARY DRAIN LINE FROM THE PAN | | | TERMINATING OVER THE ENTRANCE DOOR. | | | PLEASE NOTE, PER 2001 FBC 307.2.1, | | | CONDENSATE SHALL NOT DISCHARGE INTO A | | | STREET ALLEY OR OTHER AREAS SO AS NOT TO | | | CREATE A NUISANCE.THIS MAY CAUSE A | | | SLIP AND FALL TERMINATING INTO THE | | | ENTRANCE WAY. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|