Plan Review Notes
Plan Review Notes For Permit 05090336
Permit Number 05090336
Review Stop E
Sequence Number 1
Notes
Date Text
2005-09-26 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SUBMIT 2 COPIES OF THE GENERATOR AND
 TRANSFER SWITCH MANUFACTURERS
 SPECIFICATION.
  
 2} SUBMIT A SITE PLAN SHOWING THE
 LOCATION FO ALL SERVICE AND GENERATOR
 EQUIPMENT. THIS IS REQUIRED TO INDICATE
 COMPLIANCE WITH ARTICLES 225.31 THROUGH
 225.37.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  