Plan Review Notes
Plan Review Notes For Permit 05090332
Permit Number 05090332
Review Stop MEDGAS
Sequence Number 1
Notes
Date Text
2005-09-17 00:00:00MED-GAS DENIED;
 1
 CONTRACTOR INSTALLING AIR AND VACUUM
 SYSTEM MUST BE LICENSED TO INSTALL
 MEDICAL GAS. (ADD TO NOTES)
 2.VACUUM PIPING SHALL COMPLY WITH NFPA
 PP-C SEC. 4-5.2.2.1 (CLEANOUTS REQUIRED)
 3.AIR VENT FOR MAKE-UP AIR FOR
 COMPRESSOR SHOWN ON SHEET A-2 IS NOT
 SHOWN ON MECH. DRAWINGS. SHOWS SIZE AND
 WHERE MAKE-UP ORIGINATES FROM.
 4.EXHAUST FROM THE VACUUM SYSTEM SHALL
 BE PIPED TO THE OUTSIDE PER. NFPA 99-C
 SEC. 4-52.1.4 (SHOW ON DRAWINGS)
 5.DENTAL EQUIPMENT INSTALLATION
 INSTRUCTIONS ARE NOT WITH PLANS. PLEASE
 SUBMIT FOR REVIEW.
 6.FLOOR DRAIN IN EQUIPMENT ROOM SHOULD
 HAVE A TRAP PRIMER.
 MED-GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved