| Plan Review Notes For Permit 05090332 |
| Permit Number |
05090332 |
|
| Review Stop |
MEDGAS |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-09-17 00:00:00 | MED-GAS DENIED; | | | 1 | | | CONTRACTOR INSTALLING AIR AND VACUUM | | | SYSTEM MUST BE LICENSED TO INSTALL | | | MEDICAL GAS. (ADD TO NOTES) | | | 2.VACUUM PIPING SHALL COMPLY WITH NFPA | | | PP-C SEC. 4-5.2.2.1 (CLEANOUTS REQUIRED) | | | 3.AIR VENT FOR MAKE-UP AIR FOR | | | COMPRESSOR SHOWN ON SHEET A-2 IS NOT | | | SHOWN ON MECH. DRAWINGS. SHOWS SIZE AND | | | WHERE MAKE-UP ORIGINATES FROM. | | | 4.EXHAUST FROM THE VACUUM SYSTEM SHALL | | | BE PIPED TO THE OUTSIDE PER. NFPA 99-C | | | SEC. 4-52.1.4 (SHOW ON DRAWINGS) | | | 5.DENTAL EQUIPMENT INSTALLATION | | | INSTRUCTIONS ARE NOT WITH PLANS. PLEASE | | | SUBMIT FOR REVIEW. | | | 6.FLOOR DRAIN IN EQUIPMENT ROOM SHOULD | | | HAVE A TRAP PRIMER. | | | MED-GAS PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|