| Plan Review Notes For Permit 05090332 |
| Permit Number |
05090332 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-09-16 00:00:00 | ******** PROVISO/ REVISION ********* | | | | | | 1)NOTE: PLEASE SEE 450.3(B) FOR MAX | | | OVER-CURRENBT PROTECTION FOR 45KVA | | | TRANSFORMER. 125%) PLEASE SEE 100A BRKR | | | SHOWN. | | | | | | 2)NOTE: PLEASE SEE FEEDS TO BOTH | | | TRANSFOMERS CONTAIN NEUTRALS. PLEASE SEE | | | THESE SYSTEMS SEEM TO BE BOTH SEPARATELY | | | DERIVED SYSTEMS. | | | 450 | | | | | | PLEASE REVISE THE ABOVE INFORMATION | | | ALONG WITH ANY OTHER REVISIONS BEFORE | | | THE ROUGH ELECTRICAL INSPECTION. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|