| 2006-03-01 00:00:00 | BUILDING REVIEW SECOND CHECKLIST: |
| | 1- AS OF JANUARY 1ST 2006 ENGINEER NEEDS |
| | TO USE NEW SEAL AS REQUIRED BY RULE |
| | 61G15-23.001 OF F.A.C. |
| | SEE ATTACHED COPY. |
| | |
| | 2- PROVIDE A COMPLETE INSTALLATION |
| | SCHEDULE THAT PROVIDES ALL INFORMATION |
| | REQUIRED TO REVIEW COMPLIANCE WITH THE |
| | CALCULATED DESIGN PRESSURES AND WITH THE |
| | LIMITATIONS OF THE FLORIDA PRODUCT |
| | APPROVAL SUBMITTED. |
| | MIN. INFORMATION REQUIRED: OPENING SIZE, |
| | PROPOSED INSTALLATION OF ARMOR SCREEN |
| | (EG: STRAIGHT, STORM BAR, ANGLE, ETC), |
| | SPAN, DEFLECTION, ANCHOR TYPE AND |
| | SPACING, ETC. |
| | SECTION 104.2.1.2OF CITY AMENDMENTS TO |
| | FBC 2001. |
| | |
| | 3- ADDITIONAL DRAWING SUBMITTED FOR |
| | TYPICAL FLUSH MOUNT APPLICATION IS NOT |
| | PART OF THE DADE COUNTY NOA SUBMITTED, |
| | THEREFORE, IT CAN'T BE USED. SEE |
| | MOUNTING CONDITIONS ON DADE COUNTY NOA |
| | DRAWINGS. |
| | |
| | 4- NEED EMERGENCY EGRESS AS REQUIRED BY |
| | SEC. 1005.4.5 FBC 2001. SPECIFY HOW IS |
| | THIS ACCOMPLISHED. NEED AT LEAST ONE |
| | MEANS OF ESCAPE. HAND WRITTEN NOTE ON |
| | KEY PLAN SAYING THAT SCREEN TO BE CUT OR |
| | REMOVED IS NOT ACCEPTABLE TO COMPLY WITH |
| | SEC. 1005.4.5 FBC 2001. |
| | |
| | 5- NOTICE OF COMMENCEMENT IS EXPIRED |
| | AFTER 90 DAYS OF RECORDING IT IF WORK IS |
| | NOT STARTED. NEED RE-RECORDED NOC. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |