| Plan Review Notes For Permit 05090307 |
| Permit Number |
05090307 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-01-11 00:00:00 | ***** UNSAT ***** | | | | | | 1)NOTE: PLEASE CORRELATE RISER AND | | | PANELS. PLEASE SEE PANEL "LA" IS SHOWN | | | AS 100A S-PHASE PANEL, HOWEVER CONDUCTOR | | | ON RISER ARE SHOWN FOR A 1-PHASE PANEL? | | | | | | 2)NOTE: PLEASE SEE "EQUIPMENT GROUNDING | | | CONDUCTORS" ARE STILL BEING SHOWN BEFORE | | | THE FIRST MEANS OF DISCONNECT AS | | | PROHIBITED BY 250.6, 250.24 | | | PLEASE CLARIFY, AS PLANS SHOW A BREAKER | | | NEXT TO THESE PANELS, HOWEVER THIS IS | | | NOT REFLECTED ON RISE4R? IS THIS A MAIN | | | BRKR DISC AHEAD OF GUTTER OR PANELS? | | | IF SO, THEN THE "EQUIPMENT GROUNDING | | | CONDUCTORS WOULD REMAIN, BUT UNALBE TO | | | VERIFY AT THIS TIME. | | | PLEASE SEE E2.1 FOR THE "BREAKER" | | | INDICATED, BUT NOT ON RISER. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | PLEASE KNOW, A RESPONSE LTR AS SUBMITTED | | | BY ARCHITECTUAL FIRM MAY ALSO HELP IN | | | ANY EXPLANATION OF COMMENTS FOR | | | ENGINEERING FIRM. THIS IS NOT REQUIRED , | | | HOWEVER THIS WILL HELP IN EXPEDITING THE | | | REVIEW AND PROCESS OF PLANS. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|