Plan Review Notes
Plan Review Notes For Permit 05090307
Permit Number 05090307
Review Stop E
Sequence Number 1
Notes
Date Text
2005-09-21 00:00:00********* UNSAT **********
  
 1)NOTE: PLEASE CORRELATE RISER
 ELECTRICAL NOTES WITH RISER. PLEASE SEE
 SOME NUMBERS INDICATED ON RISER, HOWEVER
 THESE COULD NOT BE LOCATED ON NOTES.
 PLEASE SEE REDLINED PLANS.
  
 2)NOTE: PLEASE SEE "EQUIPMENT GROUNDING
 CONDUCTORS" ARE ONLY INSTALLED AFTER THE
 FIRST MEANS OF DISCONNECT. PLEASE SEE
 250.6,250.24 ETC
  
 3)NOTE: PLEASE SEE A "WALK-IN " COOLER
 IS SHOWN ON PLANS HOWEVER THERE IS NO
 INDICATION OF THIS SHOWN ON EITHER PANEL
 SCHEDULE OR LOADS INDICATED FOR POSSIBLE
 LOADS.
 PLANS SHOW A 60A DISCONNECT ONLY. IT IS
 NOTED THAT THE OCP WILL BE PER
 MANUFACTURES SPECS/ ETC HOWEVER, SOME
 INDICATION OF SIZING/LOAD SHOULD BE
 SHOWN AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  