| Plan Review Notes For Permit 05090307 |
| Permit Number |
05090307 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-09-21 00:00:00 | ********* UNSAT ********** | | | | | | 1)NOTE: PLEASE CORRELATE RISER | | | ELECTRICAL NOTES WITH RISER. PLEASE SEE | | | SOME NUMBERS INDICATED ON RISER, HOWEVER | | | THESE COULD NOT BE LOCATED ON NOTES. | | | PLEASE SEE REDLINED PLANS. | | | | | | 2)NOTE: PLEASE SEE "EQUIPMENT GROUNDING | | | CONDUCTORS" ARE ONLY INSTALLED AFTER THE | | | FIRST MEANS OF DISCONNECT. PLEASE SEE | | | 250.6,250.24 ETC | | | | | | 3)NOTE: PLEASE SEE A "WALK-IN " COOLER | | | IS SHOWN ON PLANS HOWEVER THERE IS NO | | | INDICATION OF THIS SHOWN ON EITHER PANEL | | | SCHEDULE OR LOADS INDICATED FOR POSSIBLE | | | LOADS. | | | PLANS SHOW A 60A DISCONNECT ONLY. IT IS | | | NOTED THAT THE OCP WILL BE PER | | | MANUFACTURES SPECS/ ETC HOWEVER, SOME | | | INDICATION OF SIZING/LOAD SHOULD BE | | | SHOWN AT THIS TIME. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | 2005-09-20 00:00:00 | IN ELEC FOR REVIEW. |
|