2005-11-06 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)PROVIDE INFORMATION IN REGARDS TO
 THE BUILDING (SURVEY OR SITE PLAN),
 ADJACENT TENANTS IF APPLICABLE.THIS
 APPEARS TO BE A FREE STANDING STRUCTURE
 WITH ONE SPACE, BUT BUILDING CODE
 CLASSIFICATION (ON D1 AND A1) INDICATES
 A REQUIREMENT OF 1 HOUR SEPARATION.IS
 ANY SEPARATION NECESSARY?THIS SHOULD
 BE 2 HOUR FOR FACTORY OCCUPANCY IF IT IS
 AN OCCUPANCY SEPARATION, FBC TABLE
 704.1.
  
 3.)WHAT DOES THE SOLID SINGLE LINE
 ATTACHED TO THE BUILDING REPRESENT?IT
 HAS NOT BEEN INCLUDED ON THE WALL
 LEGEND.THIS IS ADJACENT TO THE
 EXISTING OVERHEAD ELEC SERVICE AND
 ANOTHER LINE EXTENDING FROM NEAR THE
 EXISTING FIRE SPRINKLER RISER, D1 AND
 ALSO APPEARS ON A1.THE EXIT FOR THE
 BUILDING OPENS INTO THIS SPACE.
  
 4.)D1 SHOWS AN EXISTING OVERHEAD DOOR,
 BUT GRAPHICALLY SHOWS LARGE DOUBLE DOORS
 WHICH ARE MARKED AS AN EXIT ON A1 AND
 A2.PLEASE CLARIFY.FBC1012.1, THE
 DOOR WIDTH CANNOT EXCEED 48INCHES.
  
 5.)SHOW DIMENSIONS FOR ALL DOORS IN
 THE EGRESS PATH.
  
 6.)WHAT DOES ETR STAND FOR?THIS NOTE
 IS ON SOME OF THE DOORS, A1.IF YOU ARE
 GOING TO USE NON STANDARD ABBREVIATIONS,
 PLEASE INCLUDE A SCHEDULE TO AVOID
 CONFUSION.
  
 7.)PROVIDE A MORE COMPLETE PROJECT
 DESCRIPTION.
  