| Plan Review Notes For Permit 05090289 |
| Permit Number |
05090289 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-09-10 00:00:00 | ********** UNSAT ********* | | | | | | 1)NOTE: PLEASE SEE EMERGENCY LIGHT | | | FIXTURES IN BATHRMS WILL BE REQUIRED TO | | | CONTAIN A MIN OF TWO/ HEADS/BULS AS TO | | | ALLEAVIATE THE BURNING OUT OF A SINGLE | | | ELEMENT TO LEAVE ANY AREA IN TOTAL | | | DARKENES. | | | 700.16, NFPA-101 2003, 7.9. | | | | | | 2)NOTE: PLEASE INDICATE NEW OR EXISTING | | | CIRCUITING FOR NEW AND EXISTING FIXTURES | | | TO COMPLY WITH 700.12E WHICH REQUIRES | | | THE BRANCH CIRCUIT FEEDING THE UNIT | | | EQUIPMENT SHALL BE THE SAME BRANCH | | | CIRCUIT AS THAT SERVING THE NORMAL | | | LIGHTING IN THE AREA AND CONNECTED AHEAD | | | OF ANY LOCAL SWITCHES. | | | | | | PLEASE SEE ANY OTHER POSSIBLE COMMENTS | | | FROM OTHER TRADES WHICH MAY AFFECT | | | ELECTRICAL PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|