| Plan Review Notes For Permit 05090280 |
| Permit Number |
05090280 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-09-29 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1- ROOF FRAMING PLAN: REVISE CONNECTORS | | | SPECIFIED FOR TRUSSES RESTING ON GIRDER | | | TRUSS AT ENTRY ROOF. CONNECTOR SPECIFIED | | | IS FOR MASONRY APPLICATION. NEED TO | | | SPECIFY WOOD TO WOOD CONNECTORS. | | | | | | 2- TRUSS ANCHOR SCHEDULE: REVISE NUMBER | | | OF NAILS SPECIFIED FOR HUS26. SEE 2005 | | | CATALOGUE. | | | | | | 3- PROVIDE FLORIDA OR LOCAL PRODUCT | | | APPROVAL FOR: | | | A) ATRIUM 1 HR FIRE RATED DOOR WITH | | | INSWING AS SPECIFIED ON PLANS. | | | B) ROOF TILE (MISSING FLORIDA APPROVAL) | | | C) FIXED WINDOW (MISSING FL. APPROVAL) | | | D) FRENCH DOORS AT GREAT ROOM. | | | | | | 4- WINDOW MULLION SIZE SPECIFIED FOR | | | FIXED WINDOWS AT GREAT ROOM DOESN'T | | | RESIST THE DESIGN PRESSURES. REVISE AS | | | REQUIRED AND SPECIFY ANCHORS. SECTION | | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | | | | | 5- NEED RECORDED NOC. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712. |
|