| 2005-10-05 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| | |
| | 2- CLEARLY INDICATE WHICH ACCORDION TYPE |
| | IS GOING TO BE USED HR ACCORDION SHUTTER |
| | OR 6.8 ACCORDION SHUTTER. |
| | |
| | 3- CLARIFY IF ED SHOWN ON KEY PLAN |
| | STANDS FOR EGRESS DOOR OR NOT. NEED TO |
| | VERIFY FOR EMERGENCY EGRESS AS REQUIRED |
| | BY SEC. 1005.4.5 FBC 2001. |
| | |
| | 4- CLEARLY CIRCLE ON DRAWINGS SPECIFIC |
| | MOUNTING CONDITIONS OF SHUTTERS FOR THIS |
| | PROJECT. EG: WALL MOUNTED, BUILD OUT |
| | MOUNT, ETC. |
| | |
| | 5- CLEARLY MARK ON DRAWINGS ANCHOR |
| | SCHEDULE SPECIFIC ANCHOR TYPE AND |
| | SPACING TO BE USED (TO VERIFY ANCHOR |
| | SPACING SHOWN ON INSTALLATION SCHEDULE) |
| | ACCORDING TO THE DESIGN PRESSURES, MIN. |
| | EDGE DISTANCE, SHUTTER SLAT SPAN, |
| | CONNECTION TYPE AND STRUCTURE TO BE |
| | ATTACHED TO (CONCRETE BLOCK, CONCRETE OR |
| | WOOD). MARK ALL ITEMS THAT APPLY. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | |
| | 6- CLEARLY MARK ON DRAWINGS TABLE WITH |
| | MIN. GLASS SEPARATION REQUIRED FOR |
| | ACCORDION SHUTTER SELECTED. SEC. 104.2.1 |
| | 2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712. |