Plan Review Notes
Plan Review Notes For Permit 05090240
Permit Number 05090240
Review Stop B
Sequence Number 1
Notes
Date Text
2005-10-05 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- CLEARLY INDICATE WHICH ACCORDION TYPE
 IS GOING TO BE USED HR ACCORDION SHUTTER
 OR 6.8 ACCORDION SHUTTER.
  
 3- CLARIFY IF ED SHOWN ON KEY PLAN
 STANDS FOR EGRESS DOOR OR NOT. NEED TO
 VERIFY FOR EMERGENCY EGRESS AS REQUIRED
 BY SEC. 1005.4.5 FBC 2001.
  
 4- CLEARLY CIRCLE ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS OF SHUTTERS FOR THIS
 PROJECT. EG: WALL MOUNTED, BUILD OUT
 MOUNT, ETC.
  
 5- CLEARLY MARK ON DRAWINGS ANCHOR
 SCHEDULE SPECIFIC ANCHOR TYPE AND
 SPACING TO BE USED (TO VERIFY ANCHOR
 SPACING SHOWN ON INSTALLATION SCHEDULE)
 ACCORDING TO THE DESIGN PRESSURES, MIN.
 EDGE DISTANCE, SHUTTER SLAT SPAN,
 CONNECTION TYPE AND STRUCTURE TO BE
 ATTACHED TO (CONCRETE BLOCK, CONCRETE OR
 WOOD). MARK ALL ITEMS THAT APPLY.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 6- CLEARLY MARK ON DRAWINGS TABLE WITH
 MIN. GLASS SEPARATION REQUIRED FOR
 ACCORDION SHUTTER SELECTED. SEC. 104.2.1
 2 CITY AMENDMENTS TO FBC 2001.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.