| 2005-10-06 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| | |
| | 2- ROLLAFLEX SHADE: |
| | A) EVEN THOUGH THIS PRODUCT IS NOT USED |
| | FOR HURRICANE MISSILE IMPACT PROTECTION, |
| | STILL IT NEEDS TO MEET THE DESIGN |
| | CRITERIA OF SEC. 1606 FBC 2001. PRODUCT |
| | WAS DESIGNED FOR 90MPH. NEED TO COMPLY |
| | WITH THE 140MPH 3 SECOND GUST WIND LOAD |
| | DESIGN. |
| | |
| | B) WIND LOAD TABLE 3.44 IS NOT PREPARED |
| | BY THE SAME ENGINEER WHO DESIGNED THE |
| | ROLLAFLEX SHADE. NEED TO BE SIGNED AND |
| | SEALED BY THE CONSULTING ENGINEER SHOWN |
| | ON THE TITLE BLOCK AT BOTTOM OF PAGE AS |
| | REQ'D BY CHAPTER 471 OF FL. STATUTES. |
| | |
| | C) WIND LOAD TABLE 3.44: CLARIFY WHY |
| | USING TRIBUTARY AREA OF 100S.F.SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | D) PROVIDE DETAILS AND SPECIFICATIONS |
| | FOR ANCHORING OF UPPER BOX SUPPORTING |
| | THE ROLLAFLEX SHADE WHEN IT'S IN OPEN |
| | POSITION. MUST RESIST 140MPH 3 SECOND |
| | GUST WIND LOAD. SEC. 1606 FBC 2001. |
| | |
| | E) ENGINEER TO PROVIDE ALL HIS |
| | INFORMATION ON SIGNED AND SEALED |
| | DRAWINGS AS REQUIRED BY CHAPTER 471 FL. |
| | STATUTES & FLORIDA ADMINISTRATIVE CODE |
| | 61G15-23.002. |
| | |
| | F) PROVIDE SPECS/DETAILS OF HOW IS THE |
| | SHADE OPENED/CLOSED. IS IT DONE MANUALLY |
| | OR POWERED?. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. (ELECTRIC PERMIT |
| | IS REQUIRED FOR POWERED OPERATION). |
| | |
| | G) PROVIDE 2 ORIGINAL SIGNED AND SEALED |
| | DRAWINGS. NOT COPIES. CHAPTER 471 |
| | FLORIDA STATUTES. |
| | |
| | 3- IF THE INTENTION IS TO PROTECT ALL |
| | DWELLING OPENINGS, THEN CLARIFY WHY THE |
| | LARGER OPENING IS NOT GOING TO BE |
| | PROTECTED. LEAVING OPENINGS WITHOUT |
| | PROTECTION (SPECIALLY A LARGE OPENING) |
| | DECEIVES THE PURPOSE OF PROTECTING THE |
| | DWELLING. DWELLING WILL BE PARTIALLY |
| | OPEN IF THE GLASS BRAKES AND THE OTHER |
| | SHUTTERS MAY BE BLOWN AWAY BECAUSE OF |
| | THE INTERNAL PRESSURES. |
| | |