Plan Review Notes
Plan Review Notes For Permit 05090201
Permit Number 05090201
Review Stop B
Sequence Number 2
Notes
Date Text
2005-10-03 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.ITEM 1
 ON THE NOC IS TO INCLUDE THE LEGAL
 DESCRIPTION AS REQUIRED BY FLORIDA
 STATUTE.
  
 2.)ALL CHANGES TO THE PLAN ARE TO BE
 CLEARLY MARKED WITH CLOUDS AND A
 REVISION NUMBER.
  
 3.)SHOW MANEUVEURING CLEARANCE AT THE
 DOOR FBC11-4.13.6, FIGURE 25.THIS WAS
 ADDRESSED BY INDICATING 'MINIMUM 18"
 CLEAR' ON THE PLAN BUT WHEN SCALED IT IS
 LESS THAN 6".TO MAKE CODE COMPLIANCE
 CLEAR, PLEASE REVISE THE PLAN.
  
 4.)THE LICENSE NUMBER AA0003061 IS NOT
 FOR FLC ARCHITECTS ON THE FLORIDA DBPR
 WEBSITE.PLEASE CLARIFY OR REVISE THE
 TITLE BLOCK WITH THE CORRECT
 INFORMATION.
  
  
 SEE ATTACHED FS553.80(2)(B).A 4X PLAN
 REVIEW FEE WILL BE CHARGED IF THE
 COMMENTS ARE NOT ADDRESSED ON THE NEXT
 REVIEW.