| Plan Review Notes For Permit 05090187 |
| Permit Number |
05090187 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-09-29 00:00:00 | NEED PANEL SCHEDULES SHOWING BREAKER | | | SIZES AND WIRE SIZES ALSO NEED TO BRING | | | UP TO TODAYS CODE 2002 NEC | | | ARC FAULTS AND GFCI REQUIRED 210.8,12 | | | OUTLETS ON FRONT AND BACK OF EACH GRADE | | | ACCESS UNIT. | | | | | | ONLY TWO WATER HEATERS SHOWN? | | | | | | IF THIS IS TWO BUILDINGS THEN GROUND | | | RODS WILL BE REQUIRED AT THE SECOND | | | BUILDING. | | | | | | JAKE644-7291 |
|