Plan Review Notes
Plan Review Notes For Permit 05090187
Permit Number 05090187
Review Stop E
Sequence Number 2
Notes
Date Text
2005-09-29 00:00:00NEED PANEL SCHEDULES SHOWING BREAKER
 SIZES AND WIRE SIZES ALSO NEED TO BRING
 UP TO TODAYS CODE 2002 NEC
 ARC FAULTS AND GFCI REQUIRED 210.8,12
 OUTLETS ON FRONT AND BACK OF EACH GRADE
 ACCESS UNIT.
  
 ONLY TWO WATER HEATERS SHOWN?
  
 IF THIS IS TWO BUILDINGS THEN GROUND
 RODS WILL BE REQUIRED AT THE SECOND
 BUILDING.
  