2009-07-09 14:00:07BUILDING PLAN REVIEW
 PERMIT: 05090177
 ADD: 529 EL PRADO
 CONT: CARLOS GONZALEZ
 TEL: (561)644-9776
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 ROOF REVISION
 ACTION: DENIED
  
 1) ROOF DEAD LOAD OF TRUSS TOP CHORD IS 7 LBS. 1606.6.2
 DESIGN DEAD LOADS, CONCRETE TILE ALONE IS TO BE
 CONSIDERED 16 LBS PER SQ FT. PLEASE REVIEW WITH TRUSS
 ENGINEER.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  