Plan Review Notes For Permit 05090177
Permit Number 05090177
Review Stop M
Sequence Number 5
Notes
Date Text
2006-10-13 09:51:57*** DENIED ***
 1) AS NOTED IN LAST THREE REVIEWS 12-12-06 NOTE #3,
 2-1-06 NOTE #3, 10-2-06 NOTE #1. THE 10" RETURN AIR
 TRANSFER DUCT TO THE MASTER SUITE IS TO SMALL, PER 2001
 FBC/M 601.4, 2004 FBC/R M1602.4,
 PLEASE CORRECT.
 (A) THE 8" SUPPLY AIR DUCT TO THE MASTER BEDROOM
 = 50 SQ. IN., THE 4" SUPPLY AIR DUCT TO THE MASTER
 BATHROOM = 13 SQ. IN., AND THE 4' SUPPLY AIR DUCT TO
 THE MASTER CLOSET = 13 SQ. IN.. 50+13+13=
 76 SQ.IN. TIMES 1.5= 114. A 10" DUCT = 78 SQ.
 IN. A 12" DUCT= 113 SQ. IN..
  
 2) PLEASE BE ADVISED IN COMPLIANCE WITH
 F.S. 553.80(2)(B) A FOUR TIMES THE FEE HAS BEEN ADDED
 TO THE PERMIT FEES.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.