| Plan Review Notes For Permit 05090177 |
| Permit Number |
05090177 |
|
| Review Stop |
M |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2006-10-13 09:51:57 | *** DENIED *** | | | 1) AS NOTED IN LAST THREE REVIEWS 12-12-06 NOTE #3, | | | 2-1-06 NOTE #3, 10-2-06 NOTE #1. THE 10" RETURN AIR | | | TRANSFER DUCT TO THE MASTER SUITE IS TO SMALL, PER 2001 | | | FBC/M 601.4, 2004 FBC/R M1602.4, | | | PLEASE CORRECT. | | | (A) THE 8" SUPPLY AIR DUCT TO THE MASTER BEDROOM | | | = 50 SQ. IN., THE 4" SUPPLY AIR DUCT TO THE MASTER | | | BATHROOM = 13 SQ. IN., AND THE 4' SUPPLY AIR DUCT TO | | | THE MASTER CLOSET = 13 SQ. IN.. 50+13+13= | | | 76 SQ.IN. TIMES 1.5= 114. A 10" DUCT = 78 SQ. | | | IN. A 12" DUCT= 113 SQ. IN.. | | | | | | 2) PLEASE BE ADVISED IN COMPLIANCE WITH | | | F.S. 553.80(2)(B) A FOUR TIMES THE FEE HAS BEEN ADDED | | | TO THE PERMIT FEES. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|