| 2006-10-02 00:00:00 | *** DENIED *** |
| | 1) AS NOTED IN LAST TWO REVIEWS, THE |
| | RETURN AIR TRANSFER DUCT IS TO SMALL, |
| | PLEASE SEE ATTACHED COPY OF THE CODE AND |
| | CHART TO HELP WITH YOUR SIZING, SEE HIGH |
| | LIGHTED SECTION 1 1/2 TIMES THE CROSS |
| | SECTIONAL AREA (SQUARE INCHES) NOT |
| | CFM'S. PLEASE CORRECT. |
| | |
| | 2) AS REQUESTED IN LAST TWO REVIEWS |
| | PLEASE SHOW THE LOCATION OF BOTH |
| | CONDENSER UNITS ON MECHANICAL PLANS. |
| | |
| | 3) IT APPEARS ON THE MECH. PLANS THAT |
| | THE CLOTHES DRYER VENT IS TERMINATING |
| | OVER THE KITCHEN WINDOW, IF SO PLEASE |
| | CORRECT IF NOT SHOW WHERE IT TERMINATES |
| | ON MECH. PLANS. |
| | 501.2 OUTDOOR DISCHARGE. |
| | THE AIR REMOVED BY EVERY MECHANICAL |
| | EXHAUST SYSTEM SHALL BE DISCHARGED |
| | OUTDOORS AT A POINT WHERE IT WILL NOT |
| | CAUSE A NUISANCE AND FROM WHICH IT |
| | CANNOT AGAIN BE READILY DRAWN IN BY A |
| | VENTILATING SYSTEM. AIR SHALL NOT BE |
| | EXHAUSTED INTO AN ATTIC OR CRAWL SPACE. |
| | , PER 2004 FBC/M 501.2 . |
| | |
| | 4) YOUR RESPONSE TO THE LAST REVIEW IS |
| | APPRECIATED AND I SEE THAT THE AHU IS A |
| | 2.5 TON NOT A 3 TON , MY ERROR. |
| | |
| | 5) SEE ATTACHED NOTICE FS 553.80(2)(B) |
| | REGARDING FOUR TIMES THE FEE. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |